Product Introduction
Bennett HF H35 Instruction Manual
14
Figure 1.13
–
Timer & Relay
Figure 1.14
–
Pressure Switch
Figure 1.15
–
Pressure Gauge
At start up the timer board will not allow the dispenser to power up until three minutes, the gas detector must not sense Hydrogen. This
is required for a complete air change in the dispenser enclosure to eliminate any explosive gasses.
The timer board relies on a charged battery for proper operation. If the battery is discharged, the timer will have to be bypassed through
the bypass push button on the timer board as shown in
. The switch will have to be held until the battery reaches a suitable
charge level. This could take several minutes. The dispenser enclosure must be closed and have a purge pressure of at least .15 inches of
water for proper battery charging.
Figure 1.16
–
Location of timer board battery bypass switch Installation
Summary of Contents for HIGH FLOW H35
Page 12: ...Product Introduction Bennett HF H35 Instruction Manual 8 DISPENSER IDENTIFICATION NUMBER DIN...
Page 84: ...Schematics Bennett HF H35 Instruction Manual 80 CHAPTER 8 SCHEMATICS...
Page 85: ...Schematics Bennett HF H35 Instruction Manual 81...
Page 86: ...Schematics Bennett HF H35 Instruction Manual 82...
Page 87: ...Schematics Bennett HF H35 Instruction Manual 83...
Page 88: ...Schematics Bennett HF H35 Instruction Manual 84...
Page 89: ...Schematics Bennett HF H35 Instruction Manual 85...
Page 90: ...Schematics Bennett HF H35 Instruction Manual 86...
Page 91: ...Schematics Bennett HF H35 Instruction Manual 87...
Page 92: ...Schematics Bennett HF H35 Instruction Manual 88...
Page 93: ...Schematics Bennett HF H35 Instruction Manual 89...
Page 94: ...Schematics Bennett HF H35 Instruction Manual 90...
Page 95: ...Schematics Bennett HF H35 Instruction Manual 91...
Page 96: ...Schematics Bennett HF H35 Instruction Manual 92...
Page 97: ...Schematics Bennett HF H35 Instruction Manual 93...
Page 98: ...Schematics Bennett HF H35 Instruction Manual 94...