MN715J
Receiving and Installation 3-11
230VAC Single Phase Derating for Three Phase Controls
Single phase AC input power can be used to power a three phase control.
However, the continuous and peak current ratings of the control must be
reduced by 35% (derated).
Input Fuse
Wire Gauge
Control Output
Input Fuse
Wire Gauge
Control Output
Rating HP
Fast Acting
Amps
Time Delay
Amps
AWG
mm
2
0.75
10
9
14
2.08
1
12
10
14
2.08
1.5
15
15
14
2.08
2
20
17.5
14
2.08
3
25
25
12
3.31
Note: All wire sizes are based on 75
°
C copper wire, 1% line impedance. Higher
temperature, smaller gauge wire may be used per NEC and local codes.
Recommended fuses are based on 40
°
C ambient, maximum continuous
control output current and no harmonic current.
Figure 3-6 Single Phase 230VAC Power and Motor Connections
L1
L2
L1
L2
L3
Earth
* AC Motor is not provided with control.
Baldor Series 15J Control
Metal conduit should be used to
shield output wires (from T1, T2, T3
of control to T1, T2, T3 of motor).
T1
T2
T3
T1
T2 T3
G
Shield wires inside
a metal conduit.
Motor wire should be sized using the
3 phase information in Table 3Ć4.
*
Optional components not
provided with 15J Control.
*
Optional
Fusing
Summary of Contents for ID15J1F50-ER
Page 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual...
Page 5: ...iv Table of Contents MN715J...
Page 11: ...2 4 General Information MN715J...
Page 59: ...4 22 Programming and Operation MN715J...
Page 75: ...6 6 Specifications and Product Data MN715J...
Page 79: ...A 4 Dynamic Brake Hardware MN715J...
Page 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1...