4-14 Programming and Operation
MN715J
Parameter Block Definitions
Level 1 Continued
INPUT
Operating Mode
The “Operating Modes” are: Keypad, Standard Run, 7 Speed, Fan
Pump 2 Wire, Fan Pump 3 Wire, Process Control, 3 Speed Analog 2 Wire, 3 Speed
Analog 3 Wire, EPOT 2Wire, EPOT 3Wire. External connections to the control are
made at the J4 terminal strip (wiring diagrams are shown in Section 3).
ANA CMD Select
Selects the external speed reference to be used.
Potentiometer
is the simplest method of speed control. Select Potentiometer
and connect a 5K
W
pot at J4-4, J4-5, and J4-6.
0-5 or 0-10VDC
input is selected when an input voltage signal is applied to J4-7
and J4-8.
4-20mA or 0-20mA
selection should be considered if long distance is required
between the external device and the control. Current loop allows longer
cable lengths at J4-7 and J4-8 with less attenuation of the command signal.
None
no external reference is selected.
ANA CMD Inverse
“ON” will cause a low input voltage (e.g. 0VDC) to be a maximum
motor speed command and a maximum input voltage (e.g. 10VDC) to be a low
motor speed command.
“OFF” will cause a low input voltage (e.g. 0VDC) to be a low motor speed
command and a maximum input voltage (e.g. 10VDC) to be a maximum motor
speed command.
ANA CMD Offset
Provides an offset to the Analog Input to minimize signal drift. For
example, if the minimum speed signal is 1VDC (instead of 0VDC) the ANA CMD
Offset can be set to -10% so the minimum voltage input is seen by the control as
0VDC.
ANA CMD Gain
Provides a gain factor for the analog speed reference input signal.
For example, if the analog speed reference signal is 0 - 9VDC, setting the ANA
CMD Gain to 111% allows the control to see 0 - 10VDC as the input signal.
ANA CMD Filter
Provides filtering for the analog speed reference input signal. The
greater the number (0 - 6) the more noise filtering is provided. For faster
response, use a smaller number.
OUTPUT
Relay Output
N.O. and N.C. relay outputs that may be configured to any of the
following conditions:
Ready
Active when power is applied and no faults are present.
Zero Speed
Active when output frequency is less than the value of the “Zero SPD
Set Pt” Level 1 Output parameter.
At Speed Band
Active when output frequency is within the commanded range
defined by the “At Speed Band” Level 1 Output parameter.
At Set Speed
Active when output frequency is at or greater than the “Set Speed
Point” Level 1 Output parameter.
Overload
Output is active if the output current is greater than value of the Overload
Set Point parameter value.
Underload
Output is active if the output current is less than the value of the
Underload Set Point parameter.
Keypad Control
Active when control is in local (keypad) control.
Summary of Contents for ID15J1F50-ER
Page 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual...
Page 5: ...iv Table of Contents MN715J...
Page 11: ...2 4 General Information MN715J...
Page 59: ...4 22 Programming and Operation MN715J...
Page 75: ...6 6 Specifications and Product Data MN715J...
Page 79: ...A 4 Dynamic Brake Hardware MN715J...
Page 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1...