Receiving and Installation 3-19
Fan Pump 2 Wire Connection
Figure 3-13 Fan/Pump 2 Wire Connection Diagram
11
12
13
14
15
16
17
18
Forward
Reverse
Analog Select
Firestat
Freezestat
Run Command
Speed Command
Input Common
Refer to Figure 3Ć9.
J4
Refer to Table 3Ć9
See recommended terminal
tightening torques in Section 6.
Table 3-9
Function
Firestat
Freezestat
Comment
ANA CMD Select
Closed
Closed
Firestat and Freezestat are alarm
i
t th t
id ll
d
Preset
Speed 1
Open
Closed
inputs that override all speed
commands including the keypad
Preset
Speed 1
Open
Open
commands including the keypad.
Preset
Speed 2
Closed
Open
J4-11
OPEN motor decels to stop (depending on Keypad Stop mode).
CLOSED starts Forward motor rotation.
J4-12
OPEN motor decels to stop (depending on Keypad Stop mode).
CLOSED starts Reverse motor rotation.
J4-13
OPEN selects setting of “ANA CMD Select” parameter.
CLOSED selects Analog Input #1.
J4-14
OPEN selects preset speed #1 regardless of the Speed Command input J4-13.
J4-15
OPEN selects preset speed #2 regardless of the Speed Command input J4-13.
J4-16
OPEN selects direction commands from Keypad.
CLOSED selects direction commands from terminal strip.
J4-17
OPEN selects speed commanded from Keypad.
CLOSED selects terminal strip speed source (selected in the Level 1 Input block,
ANA CMD Select parameter).
Summary of Contents for ID15J1F50-ER
Page 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual...
Page 5: ...iv Table of Contents MN715J...
Page 11: ...2 4 General Information MN715J...
Page 59: ...4 22 Programming and Operation MN715J...
Page 75: ...6 6 Specifications and Product Data MN715J...
Page 79: ...A 4 Dynamic Brake Hardware MN715J...
Page 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1...