3-18 Receiving and Installation
MN715J
7 Speed Connection
Figure 3-12 7 Speed Connection Diagram
11
12
13
14
15
16
17
18
Forward
Reverse
Analog Select
Speed Select 1
Speed Select 2
Speed Select 3
External Trip
J4
Input Common
Refer to Figure 3Ć9.
See recommended terminal
tightening torques in Section 6.
Refer to Table 3Ć8
Table 3-8
Function
Speed Select 1
Speed Select 2
Speed Select 3
ANA CMD Select
Open
Open
Open
Preset
Speed 1
Closed
Open
Open
Preset
Speed 2
Closed
Closed
Open
Preset
Speed 3
Closed
Closed
Closed
Preset
Speed 4
Closed
Open
Closed
Preset
Speed 5
Open
Open
Closed
Preset
Speed 6
Open
Closed
Closed
Preset
Speed 7
Open
Closed
Open
J4-11
OPEN motor decels to stop (depending on Keypad Stop mode).
CLOSED starts Forward motor rotation.
J4-12
OPEN motor decels to stop (depending on Keypad Stop mode).
CLOSED starts Reverse motor rotation.
J4-13
OPEN selects setting of “ANA CMD Select” parameter.
CLOSED selects Analog Input #1.
J4-14
Selects preset speeds as defined in Table 3-8.
J4-15
Selects preset speeds as defined in Table 3-8.
J4-16
Selects preset speeds as defined in Table 3-8.
J4-17
If J4-17 is connected, you must set Level 2 Protection block, External Trip to
“ON” to activate the opto input.
OPEN causes an external trip fault. The control will disable and the motor
coasts to a stop. An external trip fault is displayed (also logged in the fault log).
CLOSED allows normal operation.
Summary of Contents for ID15J1F50-ER
Page 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual...
Page 5: ...iv Table of Contents MN715J...
Page 11: ...2 4 General Information MN715J...
Page 59: ...4 22 Programming and Operation MN715J...
Page 75: ...6 6 Specifications and Product Data MN715J...
Page 79: ...A 4 Dynamic Brake Hardware MN715J...
Page 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1...