B-4 Parameter Values
MN715J
Parameter Values Level 2
OUTPUT LIMITS Block
Parameter
Adjustable Range
Factory
Setting
User
Setting
MIN OUTPUT FREQ
000.0-Max Output Freq
0.00Hz
MAX OUTPUT FREQ
000.0-120.00
60.00Hz
PK CURRENT LIMIT
00.0-Peak Rated Current
Factory Set
PWM FREQUENCY
2.5, 5.0, 7.5 kHz
Factory Set
PROTECTION Block
Parameter
Adjustable Range
Factory
Setting
User
Setting
EXTERNAL TRIP
OFF, ON
OFF
FOLDBACK PROTECT
OFF, ON
OFF
MISCELLANEOUS Block
Parameter
Adjustable Range
Factory
Setting
User
Setting
RESTART AUTO/MAN
Automatic, Manual
MANUAL
RESTART FAULT/HR
00-10
0
RESTART DELAY
000-120 Seconds
0S
LANGUAGE SELECT
English, Spanish, French,
German, Italian, Portuguese
ENGLISH
FACTORY SETTING
NO, YES
NO
SECURITY CONTROL Block
Parameter
Adjustable Range
Factory
Setting
User
Setting
SECURITY STATE
OFF, Local Security
OFF
ACCESS TIMEOUT
0-600 Seconds
0 S
ACCESS CODE
0-9999
9999
MOTOR DATA Block
Parameter
Adjustable Range
Factory
Setting
User
Setting
MOTOR RATED AMPS
00.0-Max. Amps
Factory Set
MOTOR RATED SPD
0-10800RPM
1785RPM
MOTOR RATED FREQ
050.00-120.00Hz
60.00Hz
Summary of Contents for ID15J1F50-ER
Page 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual...
Page 5: ...iv Table of Contents MN715J...
Page 11: ...2 4 General Information MN715J...
Page 59: ...4 22 Programming and Operation MN715J...
Page 75: ...6 6 Specifications and Product Data MN715J...
Page 79: ...A 4 Dynamic Brake Hardware MN715J...
Page 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1...