MN715J
Receiving and Installation 3-23
3 Speed Analog 3 Wire Connection
Figure 3-17 3 Speed Analog 3 Wire Connection Diagram
11
12
13
14
15
16
17
18
Forward
Reverse
Stop
Speed Select 1
Speed Select 2
Run Command
Speed Command
Input Common
J4
Refer to Table 3Ć12
See recommended terminal
tightening torques in Section 6.
Table 3-12
Function
Speed Select 1
Speed Select 2
ANA CMD Select
Open
Open
Preset
Speed 1
Closed
Open
Preset
Speed 2
Closed
Closed
Preset
Speed 3
Open
Closed
J4-11
Momentary CLOSED starts Forward motor rotation.
J4-12
Momentary CLOSED starts Reverse motor rotation.
J4-13
Momentary OPEN motor decels to stop (depending on Keypad Stop mode).
J4-14
Selects preset speeds as defined in Table 3-12.
J4-15
Selects preset speeds as defined in Table 3-12.
J4-16
OPEN selects direction commands from Keypad.
CLOSED selects direction commands from terminal strip.
J4-17
OPEN selects speed commanded from Keypad.
CLOSED selects terminal strip speed source (selected in the Level 1 Input block,
ANA CMD Select parameter).
Summary of Contents for ID15J1F50-ER
Page 1: ...Series 15J Inverter Control 7 04 MN715J Installation and Operating Manual...
Page 5: ...iv Table of Contents MN715J...
Page 11: ...2 4 General Information MN715J...
Page 59: ...4 22 Programming and Operation MN715J...
Page 75: ...6 6 Specifications and Product Data MN715J...
Page 79: ...A 4 Dynamic Brake Hardware MN715J...
Page 86: ...Appendix C Remote Keypad Mounting Template MN715J Remote Keypad Mounting Template C 1...