background image

 Table 28: Modbus register map

Composite

Channel 1

Channel 2

Channel 3

Channel 4

Channel 5

Channel 6

Channel 7

Channel 8

Category Measure-

ments

Read/ 

write

Type

Size

Format

Reg. add.

Reg. add.

Reg. add.

Reg. add.

Reg. add.

Reg. add.

Reg. add.

Reg. add.

Reg. add.

(Dec)

(hex)

(Dec)

(hex)

(Dec)

(hex)

(Dec)

(hex)

(Dec)

(hex) (Dec) (hex)

(Dec)

(hex)

(Dec)

(hex)

(Dec)

(hex)

Correction 

factors

Reynolds 

#

R

F

2

LSW float

53

0x0034 1077 0x0434

2101

0x0834 3125 0x0C34 4149

0x1034

5173

0x1434

6197

0x1834

7221

0x1C34 8245 0x2034

K(RE)

R

F

2

LSW float

55

0x0036 1079 0x0436 2103 0x0836

3127 0x0C36

4151

0x1036 5175 0x1436

6199

0x1836

7223 0x1C36 8247 0x2036

CTL

R

F

2

LSW float

57

0x0038

1081

0x0438 2105 0x0838 3129 0x0C38 4153

0x1038

5177

0x1438

6201

0x1838

7225 0x1C38 8249 0x2038

CPL

R

F

2

LSW float

59

0x003A

1083 0x043A 2107 0x083A

3131

0x0C3A 4155

0x103A 5179 0x143A 6203

0x183A

7227 0x1C3A

8251 0x203A

CTPL

R

F

2

LSW float

61

0x003C

1085 0x043C 2109 0x083C 3133 0x0C3C 4157

0x103C

5181

0x143C 6205 0x183C

7229 0x1C3C 8253 0x203C

Tempera-

ture inputs

Supply 

temp

R

F

2

LSW float

63

0x003E

1087

0x043E

2111

0x083E

3135 0x0C3E 4159

0x103E

5183

0x143E

6207

0x183E

7231

0x1C3E 8255 0x203E

Return 

temp

R

F

2

LSW float

65

0x0040 1089 0x0440

2113

0x0840 3137 0x0C40 4161

0x1040 5185 0x1440 6209

0x1840

7233 0x1C40 8257 0x2040

Supply-

Rtn

R

F

2

LSW float

67

0x0042

1091

0x0442

2115

0x0842 3139 0x0C42 4163

0x1042

5187 0x1442

6211

0x1842

7235 0x1C42 8259 0x2042

Supply 

dens

R

F

2

LSW float

69

0x0044 1093 0x0444

2117

0x0844

3141

0x0C44 4165

0x1044 5189 0x1444

6213

0x1844

7237 0x1C44

8261 0x2044

Return 

dens

R

F

2

LSW float

71

0x0046 1095 0x0446

2119

0x0846 3143 0x0C46 4167

0x1046

5191

0x1446

6215

0x1846

7239 0x1C46 8263 0x2046

Delta h

R

F

2

LSW float

73

0x0048 1097 0x0448

2121

0x0848 3145 0x0C48 4169

0x1048 5193 0x1448

6217

0x1848

7241

0x1C48 8265 0x2048

Pressure 

inputs

Pressure 

input

R

F

2

LSW float

75

0x004A 1099 0x044A 2123 0x084A 3147 0x0C4A

4171

0x104A 5195 0x144A

6219

0x184A

7243 0x1C4A 8267 0x204A

Special 

inputs

Special 

input 1

R

F

2

LSW float

77

0x004C

1101

0x044C 2125 0x084C 3149 0x0C4C 4173

0x104C 5197 0x144C

6221

0x184C

7245 0x1C4C 8269 0x204C

Special 

input 2

R

F

2

LSW float

79

0x004E

1103

0x044E

2127

0x084E

3151

0x0C4E 4175

0x104E 5199 0x144E

6223

0x184E

7247

0x1C4E

8271

0x204E

Special 

input 3

R

F

2

LSW float

81

0x0050

1105

0x0450 2129 0x0850 3153 0x0C50 4177

0x1050 5201 0x1450 6225

0x1850

7249 0x1C50 8273 0x2050

Special 

input 4

R

F

2

LSW float

83

0x0052

1107

0x0452

2131

0x0852 3155 0x0C52 4179

0x1052 5203 0x1452

6227

0x1852

7251

0x1C52 8275 0x2052

Flow 

totals (as 

doubles)

FWD total

R

D

4

LSW 

double

129

0x0080

1153

0x0480

2177

0x0880 3201 0x0C80 4225 0x1080 5249 0x1480

6273

0x1880

7297 0x1C80

8321 0x2080

REV total

R

D

4

LSW 

double

133

0x0084

1157

0x0484

2181

0x0884 3205 0x0C84 4229 0x1084 5253 0x1484

6277

0x1884

7301

0x1C84 8325 0x2084

FWD mass

R

D

4

LSW 

double 

137

0x0088

1161

0x0488 2185 0x0888 3209 0x0C88 4233 0x1088 5257 0x1488

6281

0x1888

7305 0x1C88 8329 0x2088

REV mass

R

D

4

LSW 

double

141

0x008C 1165 0x048C 2189 0x088C 3213 0x0C8C 4237 0x108C 5261 0x148C 6285 0x188C 7309 0x1C8C 8333 0x208C

FWD 

energy

R

D

4

LSW 

double

145

0x0090

1169

0x0490 2193 0x0890 3217 0x0C90 4241

0x1090 5265 0x1490 6289

0x1890

7313

0x1C90 8337 0x2090

REV energy

R

D

4

LSW 

double

149

0x0094

1173

0x0494 2197 0x0894 3221 0x0C94 4245 0x1094 5269 0x1494 6293

0x1894

7317

0x1C94

8341 0x2094

Total time

R

D

4

LSW 

double

153

0x0098

1177

0x0498 2201 0x0898 3225 0x0C98 4249 0x1098 5273 0x1498

6297

0x1898

7321

0x1C98 8345 0x2098

STD FWD 

total

R

D

4

LSW 

double

157

0x009C

1181

0x049C 2205 0x089C 3229 0x0C9C 4253 0x109C 5277 0x149C

6301

0x189C

7325 0x1C9C 8349 0x209C

STD REV 

total

R

D

4

LSW 

double

161

0x00A0

1185

0x04A0 2209 0x08A0 3233 0x0CA0 4257 0x10A0 5281 0x14A0 6305

0x18A0

7329 0x1CA0 8353 0x20A0

STD total 

time

R

D

4

LSW 

double

165

0x00A4

1189

0x04A4 2213 0x08A4 3237 0x0CA4 4261

0x10A4 5285 0x14A4 6309

0x18A4

7333 0x1CA4 8357 0x20A4

118

Summary of Contents for Panametrics Sentinel LCT8

Page 1: ...Sentinel LCT8 User s manual...

Page 2: ...ii...

Page 3: ...Sentinel LCT8 High accuracy ultrasonic liquid flow meter for custody transfer User s manual 910 314 Rev A October 2017 iii...

Page 4: ...no content intended for this page proceed to next page iv...

Page 5: ...tag plate 4 Chapter 2 Installation 5 2 1 Installation guidelines 5 2 2 Bill of materials 5 2 3 Preparing for installation 6 2 3 1 Installation precautions 6 2 3 2 Lifting Instructions 6 2 4 Mechanical...

Page 6: ...mming 33 3 4 3 setting up the input data feeds 37 3 4 4 Setting up the API 38 3 5 Generic meter configuration 43 3 5 1 Selecting the preferred unit type 43 3 5 2 Setting up communication 44 3 5 3 Sett...

Page 7: ...ansducer problems 97 5 6 Uncertainty in flow rate for a non insulated flowcell 97 5 7 Manufacturing tests 98 5 7 1 Frequency output test 98 5 7 2 Totalizer output test 100 5 7 3 Alarm output test 102...

Page 8: ...4 6 Power consumption 110 6 4 7 Display 110 6 4 8 Outputs 110 6 4 9 Inputs 110 6 4 10 Digital interfaces 110 6 4 11 Flow computer functionality 110 6 4 12 Hazardous area certifications 110 6 4 13 CE...

Page 9: ...following link https www bakerhughesds com sales terms conditions Typographical conventions NOTE These paragraphs provide information that provides a deeper understanding of the situation but is not...

Page 10: ...he operation of the equipment Environmental compliance RoHS The Sentinel LCT8 fully complies with RoHS regulations Directive 2011 65 EU Waste Electrical and Electronic Equipment WEEE Directive Panamet...

Page 11: ...transit times is proportional to the flow velocity The Sentinel LCT8 measures this very small time difference and using various digital signal processing techniques combined with programmed pipe para...

Page 12: ...rformance specifications across a range of disturbances Use of flow conditions is normally unnecessary due to calibration methods and meter design If the need of a flow conditioner is concluded the me...

Page 13: ...Transducer 316 SS 16 7 SEN898 electronics 1 8 External conduit connections 3 4 cable glands 3 9 Upstream meter run not supplied by Panametrics N A 10 Flow conditioner optional A R 11 Downstream meter...

Page 14: ...er Vessel manufacturer serial number Ambient and fluid temperature ranges Operating pressures Hydro test pressure and date 8 Non PED Certified Ref 442 1806 panametrics com Figure 4 Specification tag p...

Page 15: ...y codes and regulations for installing electrical equipment and working with hazardous gases or flow conditions Consult company safety personnel or local safety authorities to verify the safety of any...

Page 16: ...meters will cause flow profile disturbances Make sure any non symmetrical offset does not exceed 1 as misalignment between the piping and the meter may cause flow profile disturbances Make sure the ga...

Page 17: ...p produce a more symmetrical flow profile thus further reducing measurement uncertainty Bi directional flow 3D Note temperature and pressure transmitters should Be located elsewhere for bi directional...

Page 18: ...applications where conditions are outside the above recommendations for a more comprehensive application review 2 4 3 Guidelines for installing pipe insulation If pipe insulation is required Install a...

Page 19: ...s WARNING Always disconnect the line power from the meter before removing either the front display cover or the wiring access cover This is especially important in a hazardous environment 1 Disconnect...

Page 20: ...ly accessible and located within 1 8 m 6 ft of the unit NOTE Use one conduit inlet for the power cable and use the two remaining conduit inlets for any I O cables as needed All unused conduit inlets s...

Page 21: ...ed to the next section 2 5 4 Wiring the serial port The flow transmitter is equipped with a built in serial communications port This port is user selectable to be either an RS232 or RS485 port For mor...

Page 22: ...ugh this conduit hole 3 Locate the 26 pin terminal block TB2 in Figure 29 on page 16 and wire the I O terminal as indicated on the label inside the wiring access cover see Figure 13 on page 31 and Fig...

Page 23: ...N2 AIN1 Powered transmitter RTN3 RTN3 RTN2 RTN2 RTN1 RTN1 AIN3 24V3 AIN2 24V2 AIN1 24V1 AIN3 AIN2 AIN1 Sentinel LCT8 provides 24VDC for the transmitter You can wire to either RTN1 TB connection Figure...

Page 24: ...AWG 3 3 0 2 mm2 twisted pair wire for a single conductor and 16 24 AWG 1 5 0 2 mm2 wire for a two conductor connection but the current loop impedance for these circuits must not exceed 1000 ohms To wi...

Page 25: ...ressure vessel is intended to measure fluid flow under normal operation There are no moving parts The transmitter will make continuous measurements of the flow along with ancillary inputs of temperatu...

Page 26: ...Figure 29 SEN898 electronics enclosure front display and wiring access cover Wiring Access Cover Front Display 16...

Page 27: ...Figure 30 SEN898 electronics enclosure terminal block layout ALM1 ALM2 TB3 TB1 USB J1 J2 RJ45 Ain3 Ain2 Ain1 I O TB2 in R2 in R2 in R2 Tx Rx Com Aout Aout F T1 F T1 COM NC NO 17...

Page 28: ...INPUTS OPTION AAA ANALOG INPUT 1 AIN1 ANALOG IN 24V1 24VDC RTN1 24VDC RETURN RTN1 ANALOG RETURN ANALOG INPUT 2 AIN2 ANALOG IN 24V2 24VDC RTN2 24VDC RETURN RTN2 ANALOG RETURN ANALOG INPUT 3 AIN3 ANALO...

Page 29: ...Figure 32 Wiring LCT8 to SEN898 electronics cross plane 6 24 flowcell local mount ref dwg 702 2041 19...

Page 30: ...20...

Page 31: ...wn arrow key Figure 33 Sentinel LCT8 HMI The Sentinel LCT8 HMI includes the seven keys listed in Table 3 below Table 3 Keypad symbols and descriptions Key symbol Key name Functions CLR TOTALS Clear to...

Page 32: ...hes on the front display can be locked which will lock out the ability to do any programming changes even from a PC connected to meter and the totalizer only lockout which will not allow anyone to res...

Page 33: ...ble when logged in with at least user 3 access Green dotted arrow The navigation is only possible when logged in with at least user 3 access The dotted arrow indicates that all intermediate display ch...

Page 34: ...tiple security access codes which grant different access level privileges see Table 5 below Table 5 Security level descriptions Level Security access Default passcode Privilege details 0 Full lock 000...

Page 35: ...ence and return to the locked measurement view or press the key to login an the unlocked measurement view NOTE If necessary refer to Table 4 on page 23 as a reminder about color code meanings After un...

Page 36: ...evel access The options may vary for user access levels and some pages will be entirely blank for user1 and user2 access levels General instructions From measurement view press key to go to page 2 To...

Page 37: ...vel is required to make these changes 2 Press the key to access the security options list 3 Use the and keys to highlight the desired security level option 4 Press the key twice confirm your selection...

Page 38: ...ns list at least user1 access level is required 3 Use the and keys to highlight the desired security level option 4 Press the key twice confirm your selection NOTE The example screens shown above are...

Page 39: ...status option Then press the key to confirm your selection or press the key to return to the previous screen 4 Use the and keys to highlight either the on or off option Then press the key twice to con...

Page 40: ...e tw peak pcnt option Then press the key to confirm your selection or press the key to return to the previous screen NOTE The zero cutoff parameter causes fluid velocities less than the setpoint to be...

Page 41: ...annel 2 to channel 8 highlight the option and press key twice to confirm the selection Once you confirm your selection you will see the next screen The arrow on the screen usually indicates there are...

Page 42: ...The signal min limit is the minimum acceptable value for the transducer signal received by the Sentinel LCT8 If the signal falls below the programmed limit the E1 LOW SIGNAL error is displayed The mea...

Page 43: ...ccess required to follow the step Green At least user 3 level access required to follow the step Dotted green Not all transitional screens are shown at least user 3 level access required Green Option...

Page 44: ...fluid type is the only option and is already highlighted Press the key to confirm this selection or press the key to return to the previous screen IMPORTANT Consult the factory before choosing either...

Page 45: ...n press the key to confirm your selection or press the key to return to the previous screen 4 At the next screen use the and keys to highlight the error allowed option Then press the key to confirm yo...

Page 46: ...confirm your selection or press the key to return to the previous screen 4 At the next screen use the and keys to highlight the compensation status option Then press the key to confirm your selection...

Page 47: ...level access required to follow the step Green At least user 3 level access required to follow the step Green Option only visible to user 3 or above NOTE To select composite highlight the option and...

Page 48: ...optional and this section is applicable only if the API option was ordered Use the API setup submenu by completing the following steps 1 Refer to Primary pages on page 26 and navigate to page 3 progr...

Page 49: ...the next screen Legend Red At least user 1 level access required to follow the step Green At least user 3 level access required to follow the step Green Option only visible to user 3 or above Use or...

Page 50: ...to return to the previous screen If user defined was selected as the base condition complete the following additional steps 5 At the next screen with user def base temp highlighted press the key to c...

Page 51: ...wn at least user 3 level access required Green Option only visible to user 3 or above NOTE To select composite highlight the option and press key twice to confirm the selection Once you confirm your s...

Page 52: ...the available variables Then press the key to confirm your selection or press the key to return to the previous screen c Enter the appropriate value for your application and press the key to confirm...

Page 53: ...e meanings 1 Refer to Primary pages on page 26 and navigate to page 4 configuration generic 2 Use the and keys to highlight units and press the key to confirm your choice 3 At the next screen use the...

Page 54: ...de meanings Figure 54 Communication Panalink setup Use arrow to highlight stop bits or data bits options and press to make further selection Navigation pattern similar to parity options Use or arrow t...

Page 55: ...e previous screen c Use the and keys to highlight the baud rate option and press the key to confirm your selection Then select the desired option from the list and press the key twice to confirm the s...

Page 56: ...munication settings refer to Figure 55 below and complete the steps on the next page NOTE If necessary refer to Table 4 on page 23 as a reminder about color code meanings Figure 55 Communication modbu...

Page 57: ...the word order option and press the key to confirm your selection Then select the desired option from the list and press the key twice to confirm the selection or press the key to cancel the change a...

Page 58: ...gure 56 Units selection for volumetric and totalizer output registers Legend Green At least user 3 level access required to follow the step Red At least user 1 access required to follow the step Red O...

Page 59: ...e total units option and press the key to confirm your selection Then select the desired option from the list and press the key twice to confirm the selection or press the key to cancel the change and...

Page 60: ...ight reset totals and press the key twice to confirm your choice 3 At the next screen use the and keys to highlight either the reset both or reset fwd totals or reset rev totals option Then press the...

Page 61: ...selection or press the key to cancel and return to the previous screen 4 Use the and keys to select either the yes or no option and press the key twice to confirm your selection or press the key to ca...

Page 62: ...us screen 4 If you chose to edit the setting use the and keys to highlight the desired character Then use the and keys to increment or decrement the value for that character Repeat this process until...

Page 63: ...ighlight one of the options then press the key to confirm your selection Configure each of the following options a Loop status select from list and press the twice key to confirm b Channel select from...

Page 64: ...n only visible to user 3 or above Use or arrow to highlight the preferred option and press twice to confirm selection Displayed units depend on the unit type and publisher selections Follow similar st...

Page 65: ...refer to Table 4 on page 23 as a reminder about color code meanings Legend Green At least user 3 level access required to follow the step Dotted green Not all transitional screens are shown at least...

Page 66: ...ete units of volume or time The maximum frequency the meter can deliver is 10kHz through a continuous pulse train that is linearly proportional to the minimum and maximum frequency output settings bas...

Page 67: ...in frequency output wiring Carefully select the pull up resistor to be sure it has a high enough resistance and wattage rating for the size of the power supply Use Table 7 below as a guide to select t...

Page 68: ...ngs Figure 64 Programming a frequency or totalizer output Legend Green At least user 3 level access required to follow the step Dotted green Not all transitional screens are shown at least user 3 leve...

Page 69: ...r error the chosen error level will be sent to the frequency output Table 9 Frequency output error level options Option Description Force low 4 mA Forces output to Fbase Force low 20 mA Forces output...

Page 70: ...arm output Legend Green At least user 3 level access required to follow the step Dotted green Not all transitional screens are shown at least user 3 level access required Green Option only visible to...

Page 71: ...s to highlight type and press the key to confirm your selection Then highlight and configure each of the following options see Table 11 on page 77 a Level program the units trip point dead band trip d...

Page 72: ...tion Units The alarm can be tripped on either forward or reverse flow using volumetric flow in m3 s of the selected channel The alarm determines direction by looking for a positive or negative change...

Page 73: ...ete the steps on the following page NOTE If necessary refer to Table 4 on page 23 as a reminder about color code meanings Figure 66 Setting up an analog input Legend Green At least user 3 level access...

Page 74: ...will need to enter the units base and span values for the selected parameter 6 Use the and keys to highlight cal and press the key to confirm your selection Then select either the base trim span trim...

Page 75: ...e steps on the next page NOTE If necessary refer to Table 4 on page 23 as a reminder about color code meanings Figure 67 Setting Up an RTD input Legend Green At least user 3 level access required to f...

Page 76: ...irm your selection Then select either Yes or No and press the key twice to confirm your selection or press the key to cancel and return to the previous screen Important selecting yes will reset all ca...

Page 77: ...68 below and complete the steps on the next page NOTE If necessary refer to Table 4 on page 23 as a reminder about color code meanings Figure 68 Configuring the display Legend Red At least user 1 leve...

Page 78: ...the key to cancel and return to the previous screen c Format program the width decimal min and max settings for the display in this view Then press the key to confirm your selection or press the key t...

Page 79: ...or above NOTE 1 Make sure the equipment used is properly calibrated NOTE 2 After completing calibration set the mode selection to normal Use or arrow to highlight the preferred option and press twice...

Page 80: ...set it to 4 mA b Enter the value read on the ammeter into the base trim screen c Verify that the ammeter now reads 4 mA 0 02 mA If necessary repeat these steps until the reading is correct Then press...

Page 81: ...ssary refer to Table 4 on page 23 as a reminder about color code meanings Figure 70 Setting the User configuration options Legend Red At least user 1 level access required to follow the step Red Optio...

Page 82: ...s can be modified In addition the user admin can also modify the passcode for modbus access The user 1 to user admin passcode must be four 4 characters long and the modbus access passcode must be from...

Page 83: ...ss required to follow the step Red Option only visible to user 1 or above Yellow Option only visible to user admin access Yellow At least user admin level access required to follow this step Green Opt...

Page 84: ...ntention to save restore or delete the current site file Then press the key twice to confirm your selection or press the key to cancel and return to the previous screen 7 To turn the meter off and reb...

Page 85: ...enance 4 1 Software If the software code needs to be updated we do suggest using a trained Panametrics service engineer to make sure that best practices are followed prior to during and after the new...

Page 86: ...o confirm your choice 3 Use the and keys to highlight main and press the key twice to confirm your selection After recording the version info main press the key to return to the previous screen NOTE F...

Page 87: ...site file For example restoring an accidentally saved version of the site file will overwrite the current site file and may change your meter configuration Figure 73 Version info main Layout and detai...

Page 88: ...user admin level access required to follow this step Green Option only available to user 3 or above Green At least user 3 level access required to follow the step NOTE Do not use default meter and upg...

Page 89: ...n numbers on page 76 2 Save the site file see Save restore or delete a site file on page 77 3 Set up the RS232 communication by connecting one end of a 9 pin RS232 cable to a serial port on the PC and...

Page 90: ...the Tera Term XMODEM send file selector window opens see Figure 79 on page 81 locate and select the cod extension file from your PC After selecting the cod extension file click open and the status wi...

Page 91: ...on page 81 and the meter will start up 8 The meter software update is now complete Proceed to Post Update recommendations on page 83 Figure 79 XMODEM send file selector Figure 80 XMODEM Send status le...

Page 92: ...ure 83 Tera Term indicates meter is ready to receive Update 3 When the Tera Term XMODEM send file selector window opens see Figure 13 below locate and select the cod extension file from your PC After...

Page 93: ...after the figure NOTE If necessary refer to Table 4 on page 23 as a reminder about color code meanings 1 Refer to Primary pages on page 26 and navigate to page 9 factory 2 Use the and keys to highlig...

Page 94: ...Press the key to quickly power on the meter and begin defaulting it Figure 88 Defaulting the meter during power on Press key to default meter Meter restarts quickly and starts defaulting the meter Me...

Page 95: ...eable interfaces see Figure 18 below Flanges see Servicing the pipe flange interface on page 85 Sensor ports see Servicing the sensor ports and transmitter connection on page 86 Transmitter connection...

Page 96: ...ant side view 2 Relieve potential pressure build up by loosening the pressure relief plug on the bottom of the upstream A plane sensor quadrant see Figure 91 above using a 10 mm hex drive socket or wr...

Page 97: ...1653 00 SEN898 main PCB assembly LCT8 SPARE XDCR KIT 2MHZ LCT8 transducer kit pair 2MHz for 6 8 flowcells 705 1912 00 SEN898 flow receiver PCB assembly LCT8 SPARE XDCR KIT 1MHZ LCT8 transducer kit pa...

Page 98: ...88...

Page 99: ...explains how to troubleshoot the Sentinel LCT8 Indications of a possible problem include Display of an error message on the LCD screen Erratic flow readings Readings of doubtful accuracy e g readings...

Page 100: ...liminating or correcting the most likely causes mentioned above check for these process and or flow conditions changes Excessive turbulence Discontinuities in fluid characteristics such as multi phase...

Page 101: ...ear the errors refer to the flow Info section to gather diagnostics data before contacting Panametrics W3 Velocity range The measured velocity exceeds the programmed limits This warning may be caused...

Page 102: ...totalizer and setting up totalizer sections E17 Temperature input This message indicates a temperature input error The temperature exceeds the specified limits for the analog RTD inputs or no input d...

Page 103: ...channel errors and refer to this table for recommended actions to correct those errors Refer to the more than one channel in error section for general troubleshooting guidelines E27 Inner chord s Two...

Page 104: ...s on a specific channel at any point in time Use or arrow to view current errors for other channels ch1 to ch8 This page provides error bitmap diagnostics This page displays all errors on a specific c...

Page 105: ...c P3 Use the and keys to view the active tw diagnostic data for channels 1 8 d P4 Use the and keys to view the current errors diagnostic data for channels 1 8 e P5 Use the and keys to view the error...

Page 106: ...in the fluid Cavitation can usually be controlled through proper system design The fluid must not excessively attenuate ultrasound signals Some fluids particularly those that are very viscous readily...

Page 107: ...e flowcell is measured and used for this purpose Under severe ambient conditions such as 40 C in winter the fluid temperature can be very different by up to 10 C from the pipe wall temperature This wi...

Page 108: ...ns on how to test specific IO functions 5 7 1 Frequency output test To test a frequency output refer to Figure 94 below and complete the steps on the following page NOTE If necessary refer to Table 4...

Page 109: ...us screen 5 Use the and keys to highlight frequency and press the key to confirm your choice or press the key to return to the previous screen a Use the and keys to highlight test freq and press the k...

Page 110: ...e or arrow to highlight the polarity option you want to test and press twice to confirm selection Use or arrow keys to position the cursor Use or arrow keys to increment or decrement the digits to the...

Page 111: ...esired pulse count value Then press the key to save the new value or press the key to keep the old value and return to the previous screen b Use the and keys to highlight Pulse width and press the key...

Page 112: ...he key to confirm your choice or press the key to return to the previous screen 5 With alarm state highlighted press the key to confirm the selection or press the key to return to the previous screen...

Page 113: ...urs after 1000 events have been recorded Parameter change The meter monitors all parameters that may have an impact on the flow rate measurement and records changes to those parameters in the audit lo...

Page 114: ...ional formatting may be applied in the Microsoft Excel file for enhanced readability 5 8 2 Error logs The Sentinel LCT8 error log records system error events in a user readable log file and stores tha...

Page 115: ...cifications 6 1 1 Flowcell dimensions The Sentinel LCT8 overall dimensions are shown in Figure 97 below and are listed in Table 16 on page 106 B H2 H1 ID L B A Section B B1 Figure 97 Flowcell assembly...

Page 116: ...6 508 300 30 28 20 762 712 508 600 32 29 20 813 737 508 12 150 30 30 22 762 762 559 300 32 31 22 813 788 559 600 36 31 22 915 788 559 14 150 36 32 23 915 813 585 300 38 33 23 966 839 585 600 40 33 24...

Page 117: ...ss steel These weights include the transmitter supplied with a stainless steel enclosure Table 17 Fully assembled dry weights Fully assembled dry weight Vessel nominal diameter in English lb Metric kg...

Page 118: ...614 24566 16 400 1 40 0 3 12 2 129 5172 569 22772 814 32542 18 450 1 40 0 3 12 2 165 6618 728 29137 1041 41637 20 500 1 40 0 3 12 2 206 8241 907 36285 1296 51852 24 600 1 40 0 3 12 2 301 12022 1323 52...

Page 119: ...248 F 6 2 11 Ambient temperature 40 to 60 C 40 to 140 F 6 2 12 Storage temperature 40 to 85 C 40 to 176 F 6 3 Meter body specifications 6 3 1 Meter body materials Carbon steel SA216 Gr WCB carbon ste...

Page 120: ...Two 4 20 mA analog inputs and one 100 ohm RTD input for temperature pressure and density input optional Three 4 20 mA analog inputs for temperature pressure and density input optional 6 4 10 Digital...

Page 121: ...he instructions in this appendix are followed the unit will comply with the EMC Directive 111 Table 20 Wiring modifications Connection Cable type Termination modification Transducer Shielded cable Ter...

Page 122: ...no content intended for this page 112...

Page 123: ...urrent or future problems NOTE For instructions on how to find the diagnostic parameters listed in the tables in this appendix refer to Flow info on page 94 113 B 2 User defined settings for the input...

Page 124: ...00 Hz Freq value min 0 m3 h Freq value max 2500 m3 h Freq error level Hold last Tot unit pulse 100 m3 h Tot pulse width 100 ms Tot polarity Positive Table 24 Alarm output Parameter Alarm example Alarm...

Page 125: ...h 7 Ch 8 Velocity SOS Gain SNR LV ATTEN ATw TW ATw G ATw SNR B 4 Troubleshooting diagnostics NOTE Make additional copies of this table as needed Table 26 Baseline flow rate Diagnostic Ch 1 Ch 2 Ch 3 C...

Page 126: ...entry Record complete and detailed service data for the Sentinel LCT8 in Service record below Make additional copies of this table as needed Table 27 Service record Date Description of service Perform...

Page 127: ...0x0C14 4117 0x1014 5141 0x1414 6165 0x1814 7189 0x1C14 8213 0x2014 Gain Up dB R F 2 LSW float 23 0x0016 1047 0x0416 2071 0x0816 3095 0x0C16 4119 0x1016 5143 0x1416 6167 0x1816 7191 0x1C16 8215 0x2016...

Page 128: ...1099 0x044A 2123 0x084A 3147 0x0C4A 4171 0x104A 5195 0x144A 6219 0x184A 7243 0x1C4A 8267 0x204A Special inputs Special input 1 R F 2 LSW float 77 0x004C 1101 0x044C 2125 0x084C 3149 0x0C4C 4173 0x104...

Page 129: ...5393 0x1510 6417 0x1910 7441 0x1D10 8465 0x2110 REV mass register 0 R L 2 LSW float 275 0x0112 1299 0x0512 2323 0x0912 3347 0x0D12 4371 0x1112 5395 0x1512 6419 0x1912 7443 0x1D12 8467 0x2112 REV mass...

Page 130: ...387 0x0D3A 4411 0x113A 5435 0x153A 6459 0x193A 7483 0x1D3A 8507 0x213A Modbus input Tempera ture input R W F 2 LSW float 317 0x013C 1341 0x053C 2365 0x093C 3389 0x0D3C 4413 0x113C 5437 0x153C 6461 0x1...

Page 131: ...09ATEX0072X FM13ATEX 0018X FM Global UK II 2 D Ex tD A21 IP66 T85 C Tz 40 C to 60 C IP66 FM09ATEX0072 FM Global UK EN 61326 1 2013 Group 1 Class A Industrial Electromagnetic Environments EN 61326 2 3...

Page 132: ...122...

Page 133: ...60079 14 as applicable Equipment is of type flameproof d design or flameproof with increased safety d e design and complies with EN 60079 0 2012 A11 2013 EN 60079 1 2014 EN 60079 7 2015 EN 60529 1991...

Page 134: ...code rating is dependent on the process temperature see the table below It is assumed that the external surface of the sensor body will be at worst case equal to the process temperature In all cases...

Page 135: ...i f i t r e C D E P n o N 3 0 4 1 2 4 4 f e R d e i f i t r e C D E P panametrics com panametrics com Markings shall appear on the transmitter tag plate as shown below LCT8 shown as an example 8 d x...

Page 136: ...OPTION AAA ANALOG INPUT 1 AIN1 ANALOG IN 24V1 24VDC RTN1 24VDC RETURN RTN1 ANALOG RETURN ANALOG INPUT 2 AIN2 ANALOG IN 24V2 24VDC RTN2 24VDC RETURN RTN2 ANALOG RETURN ANALOG INPUT 3 AIN3 ANALOG IN 24...

Page 137: ...Number of conductors 2 Solid max 1 5mm2 16 AWG 2 Stranded max 1 0 mm2 18 AWG All other screw terminal connections Maximum size Solid 4 0 mm2 12 AWG stranded 2 5 mm2 14 AWG Number of conductors 2 Soli...

Page 138: ...n targets across critical industries including Oil Gas Energy Healthcare Water and Wastewater Chemical Processing Food Beverage and many others Join the conversation and follow us on LinkedIn linkedin...

Reviews: