DURA
PULSE
AC Drive User Manual
A–17
Line Reactor Applications and Wiring Connections
Input Side of AC Drive
When installed on the input side of the AC Drive, line reactors will reduce line
notching, limit current and voltage spikes and surges from the incoming line, and
reduce the available short circuit current. The line reactors will also reduce
harmonic distortion from the AC Drive onto the line. Units are installed in front
of the AC Drive as shown.
Output Side of AC Drive
When installed on the output side of the AC Drive, line (load) reactors protect the
AC Drive from short circuits at the load. Voltage and current waveforms from the
AC Drive are enhanced, reducing motor overheating and noise emissions.
Single phase line reactors should not be installed on the output side of an AC Drive.
Use only three-phase reactors on drive outputs, and only for three-phase motors.
C1
T1
T2
T3
A2
B2
C2
A1
B1
GS3-4030
C1
L2
T1
T2
T3
A2
B2
C2
A1
L1
B1
L3
GS3-4030
Appendix A: Accessories
1st Ed. Rev. D 05/2013
Summary of Contents for DURAPULSE GS3-2010
Page 1: ...230V Class 1 50 Hp 460V Class 1 100 Hp User Manual AC Drive...
Page 2: ......
Page 6: ...w 4 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 8: ...Revision History DURAPULSE AC Drive User Manual h 2 BLANK PAGE...
Page 148: ...Chapter 4 AC Drive Parameters 4 80 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 241: ...DURAPULSE AC Drive User Manual A 1c Appendix A Accessories 1st Ed Rev D 05 2013...
Page 292: ...Appendix A Accessories DURAPULSE AC Drive User Manual A 52 BLANK PAGE 1st Ed Rev D 05 2013...
Page 314: ...Index i 8 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 315: ......
Page 316: ......