6–9
Chapter 6: Maintenance and Troubleshooting
DURA
PULSE
AC Drive User Manual
1st Ed. Rev. D 05/2013
Warning Messages
Error Name
Description
The AC drive temperature has exceeded
85% of the Over-temperature condition.
1. Ensure that the ambient temperature falls within the specified
temperature range.
2. Make sure that the ventilation holes are not obstructed.
3. Remove any foreign objects on the heat sinks and check for
possible dirty heat sink fins.
4. Provide enough spacing for adequate ventilation.
When the copy function is enabled (P 9.40),Write to EEPROM
fails.
Parameters have been locked: read only - cannot be set/cannot
write.
Error: The configuration is not accepted, or the parameter is locked.
Value Accepted.
This occurs when attempting to set two mutually exclusive
parameters to the same value. This is most commonly seen when
P4.00 and P4.13 are both set to the same value.
(Firmware version 1.04 or higher only.)
Write Failure
Parameter Locked
--- ERR ---
Value Accepted
Overheat Warning
Error: Duplicate
Function
Summary of Contents for DURAPULSE GS3-2010
Page 1: ...230V Class 1 50 Hp 460V Class 1 100 Hp User Manual AC Drive...
Page 2: ......
Page 6: ...w 4 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 8: ...Revision History DURAPULSE AC Drive User Manual h 2 BLANK PAGE...
Page 148: ...Chapter 4 AC Drive Parameters 4 80 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 241: ...DURAPULSE AC Drive User Manual A 1c Appendix A Accessories 1st Ed Rev D 05 2013...
Page 292: ...Appendix A Accessories DURAPULSE AC Drive User Manual A 52 BLANK PAGE 1st Ed Rev D 05 2013...
Page 314: ...Index i 8 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 315: ......
Page 316: ......