4–55
Presets Parameters
Jog Speed
Default Setting: 6.0
Range: 0.0 to 400.0 Hz
This parameter sets the speed for the Jog Command.
• The Jog Command is selected by a Multi-Function Input Terminal (P3.02 to P3.10)
set to the Jog Command function (09).
• Acceleration and deceleration times apply to the Jog Speed
The drive must be stopped to initiate this command. The Jog command cannot be
used simultaneously with an active FWD/STOP, REV/STOP, or RUN/STOP command.
The Jog function can be used in conjunction with the direction signal
(FWD/REV; P3.01 = 01 or 02) to Jog in forward and reverse directions.
Frequency
Time
Jog Speed
P5.00
Decel
Accel
Jog Operation
Command
DIx = 9
(P3.02 - P3.10)
ON
OFF
P 1.02/P 1.06
P 1.01/P 1.05
P5.00
Chapter 4: AC Drive Parameters
DURA
PULSE
AC Drive User Manual
1st Ed. Rev. D 05/2013