Chapter 4: AC Drive Parameters
4–52
Example 6: Reduced Analog Gain
This example shows how to limit the Maximum Frequency Reference by reducing
the Analog Input Gain. When the Analog Input is at its maximum value (10V or
20mA), the set-point frequency will be 50Hz. However, this reduced maximum
frequency applies only to an Analog Input Source of Frequncy Command. The
Maximum Output Frequency can still can still go to 60 Hz if controlled from the
Keypad, RS-485 interface, Jog Command, or Multi-Speed settings.
• Minimum Frequency Reference = 0Hz
• Maximum Frequency Reference = 50 Hz
Calculations
A) Max Output Frequency = (1750 rpm / 1750 rpm) x 60 Hz = 60 Hz
B) Analog Offset % = (0Hz / 50 Hz) x 100 = 0%
C) Analog Gain % = ((50 Hz – 0Hz) / 60 Hz) x 100 = 83.3%
D) Mid-point Frequency = ((50 Hz – 0Hz) / 2) + 0Hz = 25 Hz
Parameter Settings
P4.01: 00 (default) – Offset disabled
P4.02: 00 (default) – 0% Analog Input Offset
P4.03: 71.4 – 71.4% Analog Input Gain
P4.04: 00 (default) – Forward Motion Only
Results
60Hz
25Hz
0Hz
50Hz
Max. Output Frequency
Max. Frequency Reference
0V
5V
10V
-10V
0V
10V
0mA
10mA
20mA
4mA
12mA
20mA
DURA
PULSE
AC Drive User Manual
1st Ed. Rev. D 05/2013
Summary of Contents for DURAPULSE GS3-2010
Page 1: ...230V Class 1 50 Hp 460V Class 1 100 Hp User Manual AC Drive...
Page 2: ......
Page 6: ...w 4 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 8: ...Revision History DURAPULSE AC Drive User Manual h 2 BLANK PAGE...
Page 148: ...Chapter 4 AC Drive Parameters 4 80 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 241: ...DURAPULSE AC Drive User Manual A 1c Appendix A Accessories 1st Ed Rev D 05 2013...
Page 292: ...Appendix A Accessories DURAPULSE AC Drive User Manual A 52 BLANK PAGE 1st Ed Rev D 05 2013...
Page 314: ...Index i 8 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 315: ......
Page 316: ......