4–49
Example 3: Positive Offset
In this example, the Analog Input will have a positive offset while still using the
full scale of the potentiometer or other analog signal device. When the analog
signal is at its lowest value (0V, 0mA, or 4mA), the set-point frequency will be at
10Hz. When analog signal is at its maximum value (10V or 20mA), the set-point
frequency will be 60 Hz.
• Minimum Frequency Reference = 10 Hz
• Maximum Frequency Reference = 60 Hz
Calculations
A) Max Output Frequency = (1750 rpm / 1750 rpm) x 60 Hz = 60 Hz
B) Analog Offset % = (10 Hz / 60 Hz) x 100 = 16.7%
C) Analog Gain % = ((60 Hz – 10 Hz) / 60 Hz) x 100 = 83.3%
D) Mid-point Frequency = ((60 Hz – 10 Hz) / 2) + 10 Hz = 35 Hz
Parameter Settings
P4.01: 01 – Positive Input Offset Polarity
P4.02: 16.7 – 16.7% Analog Input Offset
P4.03: 83.3 – 83.3% Analog Input Gain
P4.04: 00 (default) – Forward Motion Only
Results
Maximum Output
Frequency
Positive Offset
60Hz
0Hz
10Hz
35Hz
0V
5V
10V
-10V
0V
10V
0mA
10mA
20mA
4mA
12mA
20mA
Chapter 4: AC Drive Parameters
DURA
PULSE
AC Drive User Manual
1st Ed. Rev. D 05/2013
Summary of Contents for DURAPULSE GS3-2010
Page 1: ...230V Class 1 50 Hp 460V Class 1 100 Hp User Manual AC Drive...
Page 2: ......
Page 6: ...w 4 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 8: ...Revision History DURAPULSE AC Drive User Manual h 2 BLANK PAGE...
Page 148: ...Chapter 4 AC Drive Parameters 4 80 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 241: ...DURAPULSE AC Drive User Manual A 1c Appendix A Accessories 1st Ed Rev D 05 2013...
Page 292: ...Appendix A Accessories DURAPULSE AC Drive User Manual A 52 BLANK PAGE 1st Ed Rev D 05 2013...
Page 314: ...Index i 8 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 315: ......
Page 316: ......