Chapter 4: AC Drive Parameters
4–22
Skip Frequency 1
Default Setting: 0.0
Range: 0.0 to 400.0Hz
Skip Frequency 2
Default Setting: 0.0
Range: 0.0 to 400.0Hz
Skip Frequency 3
Default Setting: 0.0
Range: 0.0 to 400.0 Hz
• P1.10, P1.11, and P1.12 determine the location of the frequency bands that will
be skipped during AC drive operation.
Skip Frequency 4
Default Setting: 0.0
Range: 0.0 to 400.0 Hz
Skip Frequency 5
Default Setting: 0.0
Range: 0.0 to 400.0 Hz
Skip Frequency Band
Default Setting: 0.0
Range: 0.0 to 20.0 Hz
This parameter determines the frequency band for a given Skip Frequency (P1.10,
P1.11, or P1.12). Half of the Skip Frequency Band is above the Skip Frequency
and the other half is below. Programming this parameter to 0.0 disables all skip
frequencies.
Output frequency
Skip Frequency 1
P 1.10
Skip Frequency 2
P 1.11
Skip Frequency 3
P 1.12
Skip Frequency
Set Point
Skip Frequency Band
P 1.17
P1.17
P1.14
P1.13
P1.12
P1.11
P1.10
DURA
PULSE
AC Drive User Manual
1st Ed. Rev. D 05/2013
Summary of Contents for DURAPULSE GS3-2010
Page 1: ...230V Class 1 50 Hp 460V Class 1 100 Hp User Manual AC Drive...
Page 2: ......
Page 6: ...w 4 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 8: ...Revision History DURAPULSE AC Drive User Manual h 2 BLANK PAGE...
Page 148: ...Chapter 4 AC Drive Parameters 4 80 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 241: ...DURAPULSE AC Drive User Manual A 1c Appendix A Accessories 1st Ed Rev D 05 2013...
Page 292: ...Appendix A Accessories DURAPULSE AC Drive User Manual A 52 BLANK PAGE 1st Ed Rev D 05 2013...
Page 314: ...Index i 8 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 315: ......
Page 316: ......