Chapter 4: AC Drive Parameters
4–58
Auto Restart after Fault
Default Setting: 00
Range: 00 to 10
After fault occurs (allowable faults: over-current OC, over-voltage OV), the AC
drive can be reset/restarted automatically up to 10 times. Setting this parameter to
0 will disable the reset/restart operation after any fault has occurred. When
enabled, the AC drive will restart with speed search, which starts at the previous
Frequency. To set the fault recovery time after a fault, please see (P6.13) base-
block time for speed search.
Momentary Power Loss
Default Setting: 00
Settings:
00
Stop operation after momentary power loss.
01
Continue operation after momentary power loss; speed search from
Speed Reference.
02
Continue operation after momentary power loss; speed search from
Minimum Speed.
Reverse Operation Inhibit
Default Setting: 00
Settings:
00
Enable Reverse Operation
01
Disable Reverse Operation
This parameter determines whether the AC Motor Drive can operate in the reverse
direction.
P6.03
This parameter will only work if the Source of Operation (P3.00) is set to something
other than 00 (Operation determined by digital keypad).
P6.02
P6.01
DURA
PULSE
AC Drive User Manual
1st Ed. Rev. D 05/2013
Summary of Contents for DURAPULSE GS3-2010
Page 1: ...230V Class 1 50 Hp 460V Class 1 100 Hp User Manual AC Drive...
Page 2: ......
Page 6: ...w 4 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 8: ...Revision History DURAPULSE AC Drive User Manual h 2 BLANK PAGE...
Page 148: ...Chapter 4 AC Drive Parameters 4 80 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 241: ...DURAPULSE AC Drive User Manual A 1c Appendix A Accessories 1st Ed Rev D 05 2013...
Page 292: ...Appendix A Accessories DURAPULSE AC Drive User Manual A 52 BLANK PAGE 1st Ed Rev D 05 2013...
Page 314: ...Index i 8 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 315: ......
Page 316: ......