4–33
Settings 10 and 11: External Base Block (N.O.) and External Base Block (N.C.)
Value 10 is for a normally open (N.O) input, and value 11 is for a normally closed
(N.C.) input.
When an External Base Block is activated, the LCD display reads ”EXT.BASE-
BLOCK,” the AC drive stops all output, and the motor will free run. When the
External Base Block is deactivated, the AC drive will start the speed search
function and synchronize with the motor speed. The AC drive will then accelerate
to the Master Frequency.
Setting 12: Second Accel/Decel Time
Multi-function Input Terminals DI3~DI11 can be set to select between
Accel/Decel times 1 and 2. Parameters P1.01 and P1.02 set Accel 1 and Decel 1
times. Parameters P1.05 and P1.06 set Accel 2 and Decel 2 times.
Frequency
Time
Multi-function
Input Terminal
On
Off
Accel 1
P1.01
Accel 2
P1.05
Decel 2
P1.06
Decel 1
P1.02
Maximum Output
Frequency P0.04
External
Base-Block
Signal
Output
Frequency
Output
Voltage
Capacitor
Discharge
Speed search starts with
the frequency reference
value
Min. Base Block
Time P6.13
speed synchronization
detection
≤15 ms
speed search operation
Chapter 4: AC Drive Parameters
DURA
PULSE
AC Drive User Manual
1st Ed. Rev. D 05/2013
Summary of Contents for DURAPULSE GS3-2010
Page 1: ...230V Class 1 50 Hp 460V Class 1 100 Hp User Manual AC Drive...
Page 2: ......
Page 6: ...w 4 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 8: ...Revision History DURAPULSE AC Drive User Manual h 2 BLANK PAGE...
Page 148: ...Chapter 4 AC Drive Parameters 4 80 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 241: ...DURAPULSE AC Drive User Manual A 1c Appendix A Accessories 1st Ed Rev D 05 2013...
Page 292: ...Appendix A Accessories DURAPULSE AC Drive User Manual A 52 BLANK PAGE 1st Ed Rev D 05 2013...
Page 314: ...Index i 8 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 315: ......
Page 316: ......