Chapter 5:
DURA
PULSE
MODBUS Communications
5–20
CLICK Port 3 MODBUS Configuration for RS-485
The following configuration example is specific for CLICK PLC CPUs.
• Configure the communication port before writing communication instructions into
the logic program.
• In CLICK programming software, open the “Comm Port Setup Details” dialog box
by choosing the Setup menu, then Comm Port Setup, then Port 2 Setup.
• From the “Port:” list box, choose “Port 3”.
• For the “Protocol:” list box, select “Modbus”.
• Set the “Node Address” to “1” to make the CLICK PLC a MODBUS master.
• Set the “Baud Rate” to “19200”
• Set the “Parity” to “Odd”.
• Set the “Stop Bit” to “1”.
• Set the “Time-out Setting” to “500ms”.
• Set the “Response Delay Time” to “0ms”.
The communication port settings are saved in the project file. The project must be
transferred to the CLICK PLC in order for any port setting changes to take effect.
DURA
PULSE
AC Drive User Manual
1st Ed. Rev. D 05/2013
Summary of Contents for DURAPULSE GS3-2010
Page 1: ...230V Class 1 50 Hp 460V Class 1 100 Hp User Manual AC Drive...
Page 2: ......
Page 6: ...w 4 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 8: ...Revision History DURAPULSE AC Drive User Manual h 2 BLANK PAGE...
Page 148: ...Chapter 4 AC Drive Parameters 4 80 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 241: ...DURAPULSE AC Drive User Manual A 1c Appendix A Accessories 1st Ed Rev D 05 2013...
Page 292: ...Appendix A Accessories DURAPULSE AC Drive User Manual A 52 BLANK PAGE 1st Ed Rev D 05 2013...
Page 314: ...Index i 8 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 315: ......
Page 316: ......