Chapter 5:
DURA
PULSE
MODBUS Communications
5–22
Configure the DirectLOGIC CPUs (continued)
DirectLOGIC MODBUS Port Configuration for DL05, D2-250(-1), or D4-450
The following configuration example is specific to the D2-250(-1) and DL05.
Refer to the appropriate CPU User Manual for the specifics on your DirectLogic
CPU.
• In DirectSOFT, choose the PLC menu, then Setup, then “Secondary Comm Port”.
• From the Port list box, choose “Port 2”.
• For the Protocol, select “MODBUS”.
• In the Timeout list box, select “800 ms”.
• Response Delay Time should be “0ms”.
• The Station Number should be set to “1” to make the D2-250(-1) or DL05 CPU a
MODBUS Master.
• The Baud Rate should be set at “9600” (or higher, if using an FA-ISOCON network
adapter module).
• In the Stop Bits list box, choose “1”.
• In the Parity list box, choose “Odd”.
The DL250 network instructions used in Master mode will access only slaves 1 to 90.
Each slave must have a unique number.
DURA
PULSE
AC Drive User Manual
1st Ed. Rev. D 05/2013
Summary of Contents for DURAPULSE GS3-2010
Page 1: ...230V Class 1 50 Hp 460V Class 1 100 Hp User Manual AC Drive...
Page 2: ......
Page 6: ...w 4 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 8: ...Revision History DURAPULSE AC Drive User Manual h 2 BLANK PAGE...
Page 148: ...Chapter 4 AC Drive Parameters 4 80 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 241: ...DURAPULSE AC Drive User Manual A 1c Appendix A Accessories 1st Ed Rev D 05 2013...
Page 292: ...Appendix A Accessories DURAPULSE AC Drive User Manual A 52 BLANK PAGE 1st Ed Rev D 05 2013...
Page 314: ...Index i 8 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Page 315: ......
Page 316: ......