AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling & Floor Type
40
3. Capacity amendment
3.1 Running range
Cooling capacity (Btu/h)
12000
18000
24000
36000
48000
60000
Power supply
220-240V~/50Hz
380-415V 3N~/50Hz
Voltage
187~242V
320~420V
Ambient temperature
Cooling
16~49
℃
Heating
-15~24
℃
3.2 Amendment coefficient of cooling capacity under different indoor/outdoor DB/WB
temperature
K1
Indoor air inlet temperature
℃
Outdoor air inlet DB temperature
℃
DB
WB
25
30
35
40
43
23
16
0.98
0.94
0.89
0.85
0.82
25
18
1.05
1
0.95
0.90
0.87
27
19
1.1
1.05
1
0.95
0.91
28
20
1.12
1.07
1.02
0.96
0.93
30
22
1.19
1.13
1.08
1.02
0.99
32
24
1.26
1.20
1.15
1.08
1.05
Actual cooling capacity calculation:
Actual cooling capacity=amendment coefficient of cooling capacity × nominal cooling capacity
——nominal cooling capacity could be found from the performance parameters list
——amendment coefficient of cooling capacity could be found from table above.
3.3 Amendment coefficient of heating capacity under different indoor/outdoor DB/WB
temperature K2
Actual heating capacity calculation:
Actual heating capacity=amendment coefficient of heating capacity × nominal heating capacity
——nominal heating capacity could be found from the performance parameters list
——amendment coefficient of heating capacity could be found from table above.
Indoor air inlet DB
temperature
℃
Outdoor air inlet WB temperature
℃
-15
-10
-5
0
7
10
15
15
0.64
0.71
0.77
0.8
1.04
1.1
1.16
20
0.59
0.66
0.72
0.76
1
1.06
1.12
25
0.55
0.62
0.69
0.71
0.96
1
1.07
Summary of Contents for AL-H18/4DR1(U)
Page 1: ...AUKS DC Inverter 1 Drive1 50HZ R410A 1 Service manual DC Inverter 1 Drive 1 50Hz R410a...
Page 5: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 5...
Page 7: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 7...
Page 21: ...AUKS DC Inverter 1 Drive1 50HZ R410A Four way cassette 21 Introduction of control board socket...
Page 55: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 55...
Page 89: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 89 AL H48 5DR1 U AL H60 5DR1 U...
Page 92: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 92 Filter board...
Page 109: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 109...
Page 121: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 121 Outdoor protection phase sequence...
Page 122: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 122 Cooling high pressure protection...
Page 123: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 123 Heating high pressure protection...
Page 124: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 124 Cooling low pressure protection...
Page 125: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 125 Heating low pressure protection...
Page 129: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 129 Sensor failure protection...
Page 131: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 131 Poor effect...
Page 132: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 132...
Page 133: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 133 Abnormal sound or viberation...
Page 134: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 134...
Page 135: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 135 Abnormal odor...
Page 137: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 137 Air conditioner water leakage...
Page 147: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 147 Wired controller XK 05...
Page 148: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 148...
Page 149: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 149 Installation of wired controller...