AUKS DC Inverter 1 Drive1 50HZ R410A Four-way cassette
13
Model
Indoor
ALCA-H48/5DR1
ALCA-H60/5DR1
Panel
MB12
MB12
Outdoor
AL-H48/5DR1(U)
AL-H60/5DR1(U)
Power Supply
V~,Hz,
Ph
380~415,50,3
380~415,50,3
Capacity
Cooling
Btu/h
51800-48000-1440
0
63000-60000-1800
0
W
15120-14000-4200
16800-16000-4800
Heating
Btu/h
56100-51000-1785
0
69300-63000-2205
0
W
17050-15500-5425
19800-18000-6300
Electric Data
Rated Cooling Power Input
W
5582-4294-1288
6479-4984-1495
Rated Heating Power Input
W
5461-4201-1260
6429-4945-1484
Rated Cooling Current
A
9.84-7.57-2.27
11.18-8.60-2.57
Rated Heating Current
A
9.68-7.45-2.23
10.95-8.42-2.54
Performance
EER
W/W
3.26
3.21
COP
W/W
3.69
3.64
Indoor Fan Motor
Model
XD80A
XD80A
Brand
Sinjun
Sinjun
Output Power x Fan quantity
W
80×1
80×1
Capacitor
uF
6
6
Speed (Hi/Mi/Lo)
r/min
695/585/495
695/585/495
Indoor Coil
a.Number Of Row
2
2
b.Tube Pitch(a)x Row Pitch(b)
mm
20.5×12.7
20.5×12.7
c.Fin Pitch
mm
1.4
1.4
d.Fin Material
Hydrophilic
aluminum fin
Hydrophilic
aluminum fin
e.Tube Outside Dia.and Material
mm
φ7
,
Inner grooved
φ7
,
Inner grooved
f.Coil Length x Height x Width
mm
2014×246×25.4
2014×246×25.4
g.Heat Exchanging Area
m
2
14.66
14.66
Indoor Unit
Indoor Air Flow (Hi/Mi/Lo)
m
3
/h
1800/1440/1260
1800/1440/1260
Noise Level(Hi/Mi/Lo)
dB(A)
50/47/41
50/47/41
Net Dimension (W*H*D)
mm
835×835×290
835×835×290
Packing Dimension (W*H*D)
mm
900×900×370
900×900×370
Net Weight
Kg
26.5
26.5
Gross Weight
Kg
30.5
30.5
Panel
Net Dimension (W*H*D)
mm
950×950×55
950×950×55
Packing Dimension (W*H*D)
mm
1000×1000×100
1000×1000×100
Net weight
Kg
5
5
Gross weight
Kg
7
7
Refrigerant Pipe
Liquid Side
mm
9.52(3/8)
9.52(3/8)
Gas Side
mm
19.05(3/4)
19.05(3/4)
Summary of Contents for AL-H18/4DR1(U)
Page 1: ...AUKS DC Inverter 1 Drive1 50HZ R410A 1 Service manual DC Inverter 1 Drive 1 50Hz R410a...
Page 5: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 5...
Page 7: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 7...
Page 21: ...AUKS DC Inverter 1 Drive1 50HZ R410A Four way cassette 21 Introduction of control board socket...
Page 55: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 55...
Page 89: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 89 AL H48 5DR1 U AL H60 5DR1 U...
Page 92: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 92 Filter board...
Page 109: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 109...
Page 121: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 121 Outdoor protection phase sequence...
Page 122: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 122 Cooling high pressure protection...
Page 123: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 123 Heating high pressure protection...
Page 124: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 124 Cooling low pressure protection...
Page 125: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 125 Heating low pressure protection...
Page 129: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 129 Sensor failure protection...
Page 131: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 131 Poor effect...
Page 132: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 132...
Page 133: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 133 Abnormal sound or viberation...
Page 134: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 134...
Page 135: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 135 Abnormal odor...
Page 137: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 137 Air conditioner water leakage...
Page 147: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 147 Wired controller XK 05...
Page 148: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 148...
Page 149: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 149 Installation of wired controller...