6. Failure code display
When AC has failure,outdoor control board
、
indoor digital tube and wire controller will display error
codes.
Indoor unit error code:
Error
code
Error code definition
Recovery
or not
Problem possible reasons
A1
Indoor ambient
temperature sensor
failure
Yes
Indoor PCB is broken
The fuse of indoor PCB is broken
temperature sensor broken , or exceed test limit
A2
Temperature sensor
about middle position
of evaporator failure
Yes
Indoor PCB is broken
The fuse of indoor PCB is broken
temperature sensor broken , or exceed test limit
A5
Indoor water pump
failure
Yes
Water pump no power
Water pump switch short-circuit or unconnected
Water pump is broken
Drain pipe block or up lean
Indoor PCB is broken
A8
Indoor unit ERRPROM
module failure
No
Indoor unit PCB is broken
Error module is broken.
A9
The communication
between indoor unit
and outdoor unit failed
No
The communication wire between indoor unit and
outdoor unit is broken.
Indoor unit power close
Indoor PCB is broken
AA
The communication
between indoor unit
and wire controller
failed
No
The communication wire between indoor unit
and outdoor unit is broken.
Indoor unit power close
Indoor PCB is broken
Wire controller is broken
Outdoor unit error code:
Error
code
Error code
definition
Recovery
or not
Problem possible reasons
C1
Ambient
temperature sensor
“Tao”failure
Yes
Temperature sensor failure or test temperature exceed
limit.
Sensor connection is incorrect.
Outdoor unit PCB failure.
C2
Defrosting
temperature sensor
“Tdef” failure
Yes
Temperature sensor failure or test temperature exceed
limit.
Sensor connection is incorrect.
Outdoor unit PCB failure.
C3
Discharge
temperature of
inverter compressor
"Td" failure
Yes
Temperature sensor failure or test temperature exceed
limit.
Sensor connection is incorrect.
Outdoor unit PCB failure.
Summary of Contents for AL-H18/4DR1(U)
Page 1: ...AUKS DC Inverter 1 Drive1 50HZ R410A 1 Service manual DC Inverter 1 Drive 1 50Hz R410a...
Page 5: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 5...
Page 7: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 7...
Page 21: ...AUKS DC Inverter 1 Drive1 50HZ R410A Four way cassette 21 Introduction of control board socket...
Page 55: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 55...
Page 89: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 89 AL H48 5DR1 U AL H60 5DR1 U...
Page 92: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 92 Filter board...
Page 109: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 109...
Page 121: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 121 Outdoor protection phase sequence...
Page 122: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 122 Cooling high pressure protection...
Page 123: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 123 Heating high pressure protection...
Page 124: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 124 Cooling low pressure protection...
Page 125: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 125 Heating low pressure protection...
Page 129: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 129 Sensor failure protection...
Page 131: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 131 Poor effect...
Page 132: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 132...
Page 133: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 133 Abnormal sound or viberation...
Page 134: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 134...
Page 135: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 135 Abnormal odor...
Page 137: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 137 Air conditioner water leakage...
Page 147: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 147 Wired controller XK 05...
Page 148: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 148...
Page 149: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 149 Installation of wired controller...