AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting
118
J4
The communication
between main PCB
and DC fan motor
drive module failure
Yes
DC fan motor drive module failure
DC fan failure
J7
Outdoor unit main
control PCB ERROM
module failure
No
Mail PCB failure
31
Module protection
(F0)
Yes
Supply voltage below level let the current excessive
Supply voltage exceed limit
Outdoor fan stop or low speed
32
Module hardware
protection
Yes
Supply voltage below level let the current excessive
Supply voltage exceed limit
Outdoor fan stop or low speed
33
Module software
protection
Yes
Supply voltage below level let the current excessive
Supply voltage exceed limit
Outdoor fan stop or low speed
34
Compressor
unconnected
Yes
The connect of driving module and DC inverter
compressor incorrect
Driving module failure
Compressor failure
35
Compressor phase
current overload
protection
Yes
Compressor overload
Compressor coil disconnect
Inverter driving board failure
Compressor failure
36
DC bus voltage
over-voltage or
under-voltage failure
Yes
Supply voltage below level
Supply voltage exceed limit
Driving module failure
37
Temperature sensor
of drive module heat
fins failure
Yes
Inverter driving board failure
38
Yes
Driving module failure
Drive module high
temperature limit
frequency failure
Compressor failure
Outdoor unit fan stop or low speed
39
Drive module high
temperature
shutdown protection
Yes
Driving module failure
Compressor failure
Temperature sensor failure
3E
DC inverter
compressor
running out of step
No
Once confirm the unrecoverable
Summary of Contents for AL-H18/4DR1(U)
Page 1: ...AUKS DC Inverter 1 Drive1 50HZ R410A 1 Service manual DC Inverter 1 Drive 1 50Hz R410a...
Page 5: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 5...
Page 7: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 7...
Page 21: ...AUKS DC Inverter 1 Drive1 50HZ R410A Four way cassette 21 Introduction of control board socket...
Page 55: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 55...
Page 89: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 89 AL H48 5DR1 U AL H60 5DR1 U...
Page 92: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 92 Filter board...
Page 109: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 109...
Page 121: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 121 Outdoor protection phase sequence...
Page 122: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 122 Cooling high pressure protection...
Page 123: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 123 Heating high pressure protection...
Page 124: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 124 Cooling low pressure protection...
Page 125: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 125 Heating low pressure protection...
Page 129: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 129 Sensor failure protection...
Page 131: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 131 Poor effect...
Page 132: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 132...
Page 133: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 133 Abnormal sound or viberation...
Page 134: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 134...
Page 135: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 135 Abnormal odor...
Page 137: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 137 Air conditioner water leakage...
Page 147: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 147 Wired controller XK 05...
Page 148: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 148...
Page 149: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 149 Installation of wired controller...