AUKS DC Inverter 1 Drive1 50HZ R410A Controller
152
2)
Setting of Indoor Model Based on Wired remote Controller
(1).Press [Filter Net Button] for 5 seconds, Indoor number “01” will be displayed in temperature zone of LCD
screen and “0101” will be displayed in timing setting zone of LCD screen.
“01” means that indoor unit is 01; “0101” means this parameter number is 01 and the parameter value is 01.
(2).Press [+/- Button of Clock], the parameter No. and value “0201”, “0301”, “0401” will be displayed
successively. See the table below for number of parameters and corresponding value meaning.
(3).Then press [Mode Button] once, “corresponding parameter value 01” will flicker; press [+/-button of time] to
change the value into “05”, press [Mode Button] to confirm. This parameter is changed to 05.
If there is no operation for 15 seconds, then automatically exit and keep the previous setting.
3)
Setting of Indoor Model Based on Wired remote Controller
Indoor Model
Type setting
【
04
】
Capacity setting
【
05
】
Duct Type
ALMD-H18/4DR1
12
18
ALMD-H24/4DR1
12
23
ALMD-H36/4DR1
12
36
ALMD-H48/5DR1
12
50
ALMD-H60/5DR1
12
60
4-way
Cassette
ALCA-H18/4DR1
10
18
ALCA-H24/4DR1
11
23
ALCA-H36/4DR1
11
36
ALCA-H48/5DR1
11
50
ALCA-H60/5DR1
11
60
Ceiling floor
ALCF-H18/4DR1
13
18
ALCF-H24/4DR1
13
23
ALCF-H36/4DR1
13
36
ALCF-H48/5DR1
13
50
ALCF-H60/5DR1
13
60
Indoor NO.
Parameter NO.
Clock +/- button
Corresponding
parameter value
Filter Net button
Temp +/- button
Mode button
Summary of Contents for AL-H18/4DR1(U)
Page 1: ...AUKS DC Inverter 1 Drive1 50HZ R410A 1 Service manual DC Inverter 1 Drive 1 50Hz R410a...
Page 5: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 5...
Page 7: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 7...
Page 21: ...AUKS DC Inverter 1 Drive1 50HZ R410A Four way cassette 21 Introduction of control board socket...
Page 55: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 55...
Page 89: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 89 AL H48 5DR1 U AL H60 5DR1 U...
Page 92: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 92 Filter board...
Page 109: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 109...
Page 121: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 121 Outdoor protection phase sequence...
Page 122: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 122 Cooling high pressure protection...
Page 123: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 123 Heating high pressure protection...
Page 124: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 124 Cooling low pressure protection...
Page 125: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 125 Heating low pressure protection...
Page 129: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 129 Sensor failure protection...
Page 131: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 131 Poor effect...
Page 132: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 132...
Page 133: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 133 Abnormal sound or viberation...
Page 134: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 134...
Page 135: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 135 Abnormal odor...
Page 137: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 137 Air conditioner water leakage...
Page 147: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 147 Wired controller XK 05...
Page 148: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 148...
Page 149: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 149 Installation of wired controller...