AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit
101
8.2 Connection piping installation
Piping installation precaution
Please choose the phosphorus deoxidation seamless copper pipe as the piping.
◇
If use the lengthen piping needs welding:
Please welding before fasten the nut, when welding using nitrogen gas to replace the air in the pipe in
order to prevent oxidation.
◇
If there are many points to be welded when installing the lengthen piping, please set a filter in the
pipe(buy from local market)
◇
Please use nitrogen gas or air to remove the dust and water in the pipe,
◇
Please lay out the piping according to the tend towards of the piping, but it is not allowed more than 3
times curved at the same point of the pipe(if do like this the pipe will become rigid)
◇
Pipe bending machine is used during the process of bending the pipe, the curvature shall not be too
small or it will affect the refrigerant flow.
Piping specification selection
As to the detail selection please take reference to the cooling capacity adjust index figure during different
installation situations.
Piping diameter
Tighten torque
Expanding size
(A)
Expanding shape
Paint the frozen oil
1/4in(φ6.35mm)
15-19(N·m)
8.3-8.7mm
3/8in(φ9.52mm)
35-40(N·m)
12.0-12.4mm
1/2in(φ12.7mm)
50-60(N·m)
15.4-15.8mm
5/8in(φ15.88mm)
62-76(N·m)
18.6-19.0mm
3/4in(φ19.05mm)
70-75(N·m)
22.9-23.3mm
Piping connection
◇
Using expanding machine to expand accessories, the size of horn shown in the above figure:
◇
Paint a thin layer of frozen oil at both inside and outside part of the expanding.
◇
Make the expanding right to the screw thread shape connection of the indoor unit, using hands to
tighten the nut then using a wrench to tighten the nut again, the tighten torque as follows figure.
◇
Take out the cover of the indoor unit gas valve and liquid valve, make the expanding right to the stop
valve of outdoor unit, using hands to tighten the nut then using a wrench to tighten the nut again, the
tighten torque as follows figure.
Equivalent pipe length conversion
Equivalent pipe length means converting pipe elbow to straight pipe length after considerate the
pressure loss.
Summary of Contents for AL-H18/4DR1(U)
Page 1: ...AUKS DC Inverter 1 Drive1 50HZ R410A 1 Service manual DC Inverter 1 Drive 1 50Hz R410a...
Page 5: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 5...
Page 7: ...AUKS DC Inverter 1 Drive1 50HZ R410A General description 7...
Page 21: ...AUKS DC Inverter 1 Drive1 50HZ R410A Four way cassette 21 Introduction of control board socket...
Page 55: ...AUKS DC Inverter 1 Drive1 50HZ R410A Ceiling Floor Type 55...
Page 89: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 89 AL H48 5DR1 U AL H60 5DR1 U...
Page 92: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 92 Filter board...
Page 109: ...AUKS DC Inverter 1 Drive1 50HZ R410A Universal outdoor unit 109...
Page 121: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 121 Outdoor protection phase sequence...
Page 122: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 122 Cooling high pressure protection...
Page 123: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 123 Heating high pressure protection...
Page 124: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 124 Cooling low pressure protection...
Page 125: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 125 Heating low pressure protection...
Page 129: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 129 Sensor failure protection...
Page 131: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 131 Poor effect...
Page 132: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 132...
Page 133: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 133 Abnormal sound or viberation...
Page 134: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 134...
Page 135: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 135 Abnormal odor...
Page 137: ...AUKS DC Inverter 1 Drive1 50HZ R410A Trouble shooting 137 Air conditioner water leakage...
Page 147: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 147 Wired controller XK 05...
Page 148: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 148...
Page 149: ...AUKS DC Inverter 1 Drive1 50HZ R410A Controller 149 Installation of wired controller...