Site Preparation
Centellis 2100 Shelf Release 3.0 Installation and Use (6806800T37D
)
72
2.2.2
Power Requirements
For AC, make sure that 100 VAC to 240 VAC (90 VAC to 254 VAC) rated power source is within
reach of the system, and for DC make sure that a suitable -48.0 VDC to -60 VDC rated power
source is within reach of the system. Up to two Power Supply Units (PSUs)/Power Entry
Modules (PEMs) can be installed in the system.
Personal Injury or System Damage
Centellis 2100 AC:
The system is supplied by an AC voltage. External wiring shall be compliant to all
requirements of National Electric Code (NEC).
Centellis 2100 DC:
The system is supplied by a TNV-2 voltage. This voltage is considered hazardous. Make sure
that the external power supply meets the relevant safety standards. Ensure that TNV-2 is
separated from dangerous voltages (mains) through double or reinforced insulation.
Table 2-3 AC Shelf Power Requirements
FRU
Nominal
Power (W) Shelf
Only
Maximum
Power (W) Shelf
with Payload
PSU Subsystem
6.15
144
Fan Subsystem
28
140
10G Uplink Subsystem
7
16
Shelf Management
6
20
ATCA Blades
(Two at 400 W or one at 500 W and one
at 300 W)
800
Total Shelf Power
47.15
1120
Summary of Contents for Centellis 2100 Shelf Release 3.0
Page 1: ...Centellis 2100 Shelf Release 3 0 Installation and Use P N 6806800T37D August 2017...
Page 8: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Contents 8 Contents Contents...
Page 10: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 10 List of Tables...
Page 12: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 12 List of Figures...
Page 32: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Safety Notes 32...
Page 46: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Sicherheitshinweise 46...
Page 66: ...Introduction Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 66...
Page 112: ...FRU Installation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 112...
Page 124: ...FRU Installation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 124...
Page 132: ...Cooling Subsystem Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 132...
Page 140: ...Power Subsystem Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 140...
Page 174: ...Redundancy Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 174...
Page 186: ...Troubleshooting Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 186...
Page 188: ...Related Documentation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 188...
Page 189: ......