System Installation
Centellis 2100 Shelf Release 3.0 Installation and Use (6806800T37D)
87
7. Check the AC PSU Status LED and take the appropriate actions as listed in the table
below.
3.2.3.2
DC System Startup Procedure
Depending on the system configuration, the actual powering up may take up to 3 minutes.
Make sure that the system has been placed in a location at room temperature for at least
24 hours before powering it up.
1. Put on an ESD wrist strap.
2. Connect the strap to the shelf by attaching the front or rear ESD jack/ESD snap.
3. Plug the power cord into a grounded (earthed) electrical outlet that is easily
accessible at all times.
PSU Status LED
Status
LED (red) off
Reason
: The power is disconnected.
Action
: Turn off the feed power and attach the power cables at the
power connector.
LED (red) on
LED (green) off
Power supply is in a failed state.
LED (red) off
LED (green) on
The power is connected correctly.
Summary of Contents for Centellis 2100 Shelf Release 3.0
Page 1: ...Centellis 2100 Shelf Release 3 0 Installation and Use P N 6806800T37D August 2017...
Page 8: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Contents 8 Contents Contents...
Page 10: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 10 List of Tables...
Page 12: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 12 List of Figures...
Page 32: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Safety Notes 32...
Page 46: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Sicherheitshinweise 46...
Page 66: ...Introduction Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 66...
Page 112: ...FRU Installation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 112...
Page 124: ...FRU Installation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 124...
Page 132: ...Cooling Subsystem Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 132...
Page 140: ...Power Subsystem Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 140...
Page 174: ...Redundancy Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 174...
Page 186: ...Troubleshooting Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 186...
Page 188: ...Related Documentation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 188...
Page 189: ......