Power Subsystem
Centellis 2100 Shelf Release 3.0 Installation and Use (6806800T37D
)
134
7.1.3
Power Distribution
The shelf has two different power distribution systems. The first is a management power
system (3.4 VDC) that provides power to IPMCs on shelf FRUs (fan trays and user cards) and to
the ATCA-MF106 hubs. The second is a high power system (-48 VDC) that provides power to all
blades, fans trays, shelf managers and user cards.
7.1.3.1
Management Power Distribution
The shelf's management power distribution system is used for powering the IPMCs engines of
shelf FRUs. This power source (3.4 V DC) is distributed in the shelf via a redundant
interconnection. The first (V_A) is sourced from MF106-1, the second (V_B) from MF106-2.
The IPMCs are expected to OR the two sources to allow redundancy. Current on each source is
limited to 1 A.
The
Figure "Two-PSU Shelf Power Distribution" on page 135
illustrates the PSU low power
distribution of system in the shelf, and
Figure "Two-PEM Shelf Power Distribution" on page 137
illustrates the PEM low power distribution of system in the shelf.
7.1.3.2
High Power Distribution
The shelf's high power distribution system is used for powering the blades, ShMCs, fan trays
and user cards. This high power source (-48 V DC - nominal) manifests itself in a redundant
interconnect.
7.1.3.3
AC Power Interconnect
The redundant interconnect is made up of PSU1 and PSU2 output supply. The first supply (-48
V_A) is sourced from PSU1 on the left-hand side (as viewed from the front of the shelf). The
second supply (-48 V_B) is sourced from PSU2 on the right-hand side. Both supplies are
individually routed to each ShMC, fan tray, node and user card slot. In both interconnects, the
FRUs are expected to OR the two sources to allow for redundancy.
The PSUs are capable of supplying 16 A of current.
Summary of Contents for Centellis 2100 Shelf Release 3.0
Page 1: ...Centellis 2100 Shelf Release 3 0 Installation and Use P N 6806800T37D August 2017...
Page 8: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Contents 8 Contents Contents...
Page 10: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 10 List of Tables...
Page 12: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 12 List of Figures...
Page 32: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Safety Notes 32...
Page 46: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Sicherheitshinweise 46...
Page 66: ...Introduction Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 66...
Page 112: ...FRU Installation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 112...
Page 124: ...FRU Installation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 124...
Page 132: ...Cooling Subsystem Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 132...
Page 140: ...Power Subsystem Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 140...
Page 174: ...Redundancy Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 174...
Page 186: ...Troubleshooting Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 186...
Page 188: ...Related Documentation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 188...
Page 189: ......