4.8.1
Replacing the System Filters
The shelf is equipped with two air filters which are located below and above the front fan tray.
System Damage
Air Filters
Air contamination can pollute the air filters and obstruct the air intake of the system which
may cause system overheating and component damage.
To guarantee proper airflow through the system the air filters have to be replaced at least
every six months. Artesyn recommends to replace the air filters every 90 days. Filter
replacement frequency depends on the environment the system is subjected to.
Because central offices vary in physical location and cleanliness, check your air filters every
week after you first install your system. In a dusty environment, filter replacement may be
required more often than in a cleaner environment. Check the filters frequently until you
have a good idea of how often they must be replaced. Based on your findings, establish a
regular replacement schedule and keep a log to record the date of each filter replacement.
Filter Frames
Wrong insertion may damage the frame or the guides.
When inserting the filter frame into the shelf, pay attention to insert the appropriate
bottom or top frame and to align it accurately to the guides.
Damage of Circuits
Electrostatic discharge and incorrect installation and removal of the product can damage
circuits or shorten their life.
Before touching the product make sure that your are working in an ESD-safe environment
or wear an ESD wrist strap or ESD shoes. Hold the product by its edges and do not touch any
components or circuits.
If you want to replace both the filters at the same time, exchange the top filter first. This
prevents spoiling of the new bottom filter by dust falling down when removing the top
filter.
You can order replacement filters from Artesyn, for details refer to
Summary of Contents for Centellis 2100 Shelf Release 3.0
Page 1: ...Centellis 2100 Shelf Release 3 0 Installation and Use P N 6806800T37D August 2017...
Page 8: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Contents 8 Contents Contents...
Page 10: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 10 List of Tables...
Page 12: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 12 List of Figures...
Page 32: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Safety Notes 32...
Page 46: ...Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D Sicherheitshinweise 46...
Page 66: ...Introduction Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 66...
Page 112: ...FRU Installation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 112...
Page 124: ...FRU Installation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 124...
Page 132: ...Cooling Subsystem Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 132...
Page 140: ...Power Subsystem Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 140...
Page 174: ...Redundancy Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 174...
Page 186: ...Troubleshooting Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 186...
Page 188: ...Related Documentation Centellis 2100 Shelf Release 3 0 Installation and Use 6806800T37D 188...
Page 189: ......