Figure. 5.4.9. - 52. Trip, Retrip and CBFP are con gured to the IED.
In application where the circuit breaker has retrip / redundant trip coil available, retrip functionality can
be used. The trip signal is wired normally to the trip coil of the breaker from the trip output of the IED.
Retrip is wired in parallel from its own output contact in the IED to the second tripping coil of the circuit
breaker. CBFP signal to upstream is wired normally from its output contact in the IED to the upstream /
incomer breaker. In following are few operational cases presented regarding to the different
applications.