Figure. 5.4.14. - 84. Block setting operation example. If Block setting is set to zero blocking is not in use.
Real-time info displayed by the function
The relays Info-page displays useful information in real time of the state of the protection function either
through relays HMI display or with AQtivate software when connection there is a connection to relay
and Live Edit-mode is activated.
Table. 5.4.14. - 134. Info displayed by the function
Name
Unit
Description
U1/2 >/< Pick-up
setting
V
Primary voltage required for tripping. The displayed pick-up voltage level depends on the pick-
up setting and the voltage transformer settings.
Expected
operating time
s
Displays the expected operating time in case a fault occurs
Time remaining to
trip
s
When the relay has picked up and is counting time towards pick-up
Umeas/Uset at
the moment
Um/Uset Ratio between measured voltage and the pick-up value.
Function blocking
In the blocking element the block signal is checked in the beginning of each program cycle. Blocking
signal is received from the blocking matrix for the function dedicated input. If the blocking signal is not
activated when the pick-up element activates, a START signal is generated and the function proceeds
to the time characteristics calculation.
If blocking signal is active when pick-up element activates a BLOCKED signal will be generated and the
function shall not process the situation further. If START function has been activated before blocking
signal it will reset and the release time characteristics are processed as in case of when pick-up signal
is reset.
From blocking of the function a HMI display event as well as time stamped blocking event with
information of the startup voltage values and fault type is issued.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
144