Table. 5.2.1. - 5. Phase polarity problems are easy to nd since the vector diagram points out the opposite polarity in the wrongly
connected phase.
Phase L1 (A) polarity incorrect.
Phase currents
IL1: 1.00 xIn / 0.00 deg
IL2: 1.00 xIn / 60.00 deg
IL3: 1.00 xIn / 300.00 deg
Sequence currents
I1: 0.33 xIn / 180.00 deg
I2: 0.67 xIn / 0.00 deg
I0Calc: 0.67 xIn / 0.00 deg
Resolution:
- Change wires to opposite in CT module connectors 1 – 2
- Or from the Transformers, Phase CT scaling select IL1 polarity to “Invert”.
Phase L2 (B) polarity incorrect.
Phase currents
IL1: 1.00 xIn / 0.00 deg
IL2: 1.00 xIn / 60.00 deg
IL3: 1.00 xIn / 120.00 deg
Sequence currents
I1: 0.33 xIn / 0.00 deg
I2: 0.67 xIn / -60.00 deg
I0Calc: 0.67 xIn / 60.00 deg
Resolution:
- Change wires to opposite in CT module connectors 3 – 4
- Or from the Transformers, Phase CT scaling select IL2 polarity to “Invert”.
Phase L3 (C) polarity incorrect.
Phase currents:
IL1: 1.00 xIn / 0.00 deg
IL2: 1.00 xIn / 240.00 deg
IL3: 1.00 xIn / 300.00 deg
Sequence currents:
I1: 0.33 xIn / 0.00 deg
I2: 0.67 xIn / 60.00 deg
I0Calc: 0.67 xIn / -60.00 deg
Resolution:
- Change wires to opposite in CT module connectors 5 – 6
- Or from the Transformers, Phase CT scaling select IL3 polarity to “Invert”.