Figure. 5.4.21. - 96. Ambient temperature coef cient calculation examples when reference temperature is +15 C with 3 point
linear approximation and settable correction curve.
This mentioned ambient temperature coef cient relates to nominal temperature reference. By default is
used +15 C (ground dug cables) which gives coef cient value of 1.00 for the thermal replica.
Settable thermal capacity curve uses linear interpolation for ambient temperature correction with
maximum 10 pairs of temperature – correction factor pairs.
Figure. 5.4.21. - 97. Example of the ground temperature and correction coef cient.
In the manufacturer given data the temperature coef cient may be informed as in gure above.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
168