System f.
Used tracking frequency at the moment
Ref f1
Reference frequency 1
Ref f2
Reference frequency 1
M thermal T
Motor thermal temperature
F thermal T
Feeder thermal temperature
T thermal T
Transformer thermal temperature
RTD meas 1…16
RTD measurement channels 1…16
Ext RTD meas 1…8
External RTD measurement channels 1…8 (ADAM module)
Reported values
When triggered function will hold the recorded values of the set up 8 channels. In addition to this
tripped stage, overcurrent fault type and voltage fault types are reported to SCADA.
Table. 5.6.8. - 246. Reported values of measurement value recorder
Name
Range
Step
Description
Tripped stage
0:-
1:I> Trip
2:I>> Trip
3:I>>> Trip
4:I>>>> Trip
5:IDir> Trip
6:IDir>> Trip
7:IDir>>> Trip
8:IDir>>>> Trip
9:U> Trip
10:U>> Trip
11:U>>> Trip
12:U>>>> Trip
13:U< Trip
14:U<< Trip
15:U<<< Trip
16:U<<<< Trip
-
Tripped stage
Overcurrent fault type
0:-
1:A-G
2:B-G
3:A-B
4:C-G
5:A-C
6:B-C
7:A-B-C
-
Overcurrent fault type
Voltage fault type
0:-
1:A(AB)
2:B(BC)
3:A-B(AB-BC)
4:C(CA)
5:A-C(AB-CA)
6:B-C(BC-CA)
7:A-B-C
-
Voltage fault type
Magnitude 1…8
0.000…1800.000A/V/p.u.
0.001A/V/p.u.
Recorded value in one of the eight channels.
Events
VREC function generates events from function triggering. To main event buffer it is possible to select
“On” or “Off” status messages.
Table. 5.6.8. - 247. Event codes of the VREC function.
Event Number
Event channel
Event block name
Event Code
Description
AQ-F255
Instruction manual
Version: 2.00
299
© Arcteq Relays Ltd