De nite
operating time
delay
0.000...1800.000s 0.005s 0.040s
De nite time operating delay. Setting is active and visible when
Delay Type is selected to DT.
When set to 0.000 s the stage operates as instant (PIOC, 50)
stage without added delay. When the parameter is set to 0.005 –
1800 s the stage operates as independent delayed (PTOC, 51).
Delay curve
series
IEC
IEEE
Non-standard
-
IEC
Setting is active and visible when Delay Type is selected to IDMT.
Delay curve series for IDMT operation following either IEC or
IEEE/Ansi standard de ned characteristics. Non-standard
characteristics include delay curves outside of the two sandards.
Delay
characteristics
IEC
NI
EI
VI
LTI
Param
-
NI
Setting is active and visible when Delay Type is selected to IDMT.
IEC standard delay characteristics. Normally Inverse, Extremely
Inverse, Very Inverse and Long Time Inverse characteristics.
Param selection allows the tuning of the constants A and B which
allows setting of characteristics following the same formula as the
IEC curves mentioned here.
Delay
characteristics
IEEE
LTI
LTVI
LTEI
MI
VI
EI
STI
STEI
Param
-
LTI
Setting is active and visible when Delay Type is selected to IDMT.
IEEE standard delay characteristics. Long Time Inverse, Long Time
Very Inverse, Long Time Extremely Inverse, Moderately Inverse,
Very Inverse, Extremely Inverse, Short Time Inverse, Short Time
Extremely Inverse characteristics. Param selection allows the
tuning of the constants A, B and C which allows setting of
characteristics following the same formula as the IEEE curves
mentioned here.
Non standard
delay char.
RI-type
RD-type
Curve2
-
RI-type
Non-standard RI-type, RD-type and Curve2
Time dial
setting k
0.01…25.00s
0.01s
0.05s
Setting is active and visible when Delay Type is selected to IDMT.
Time dial / multiplier setting for IDMT characteristics.
A
0.0000…
250.0000
0.0001 0.0860
Setting is active and visible when Delay Type is selected to IDMT.
Constant A for IEC/IEEE characteristics.
B
0.0000…5.0000
0.0001 0.1850
Setting is active and visible when Delay Type is selected to IDMT.
Constant B for IEC/IEEE characteristics.
C
0.0000…
250.0000
0.0001 0.0200
Setting is active and visible when Delay Type is selected to IDMT.
Constant C for IEEE characteristics.
K
0.0000…
250.0000
0.0001 0.0200
Setting is active and visible when selected delay curve is Curve1.
Constant K for Curve1 characteristics.
Table. 5.4.7. - 91. Reset time characteristics setting parameters.
Name
Range
Step
Default
Description
Release Time
delay
0.000…
150.000s 0.005s 0.06s
Resetting time. Time allowed in between of pick-ups if the pick-up has not
lead into trip operation. During this time the start signal is held on for the
timers if delayed pick-up release is active.
Delayed Pick-
up release
No
Yes
-
Yes
Resetting characteristics selection either time delayed or instant after pick-
up element is released. If activated the start signal is reset after set release
time delay.
Time calc
reset after
release time
No
Yes
-
Yes
Operating timer resetting characteristics selection. When active the
operating time counter is reset after set release time if pick-up element is
not activated during this time. When disabled the operating time counter is
reset directly after the pick-up element reset.
Continue time
calculation
during release
time
No
Yes
-
No
Time calculation characteristics selection. If activated the operating time
counter is continuing until set release time even the pick-up element is reset.
AQ-F255
Instruction manual
Version: 2.00
95