Blocking signal can be tested also in the commissioning phase of the stage by software switch signal
when relay common and global testing mode is activated.
User settable variables are binary signals from the system. Blocking signal needs to reach the IED
minimum of 5 ms before the set operating delay has passedfor blocking to be active in time.
Operating time characteristics for trip and reset
This function supports de nite time delay (DT) and inverse de nite minimum time (IDMT) delay types.
For detailed information on these delay types refer to chapter General properties of a protection
function.
Events and registers
The VUB function generates events and registers from the status changes of start, trip and blocked. To
main event buffer is possible to select status “On” or “Off” messages. The VUB function offers four
independent instances which events are segregated for each instance operation.
In the function is available 12 last registers where the triggering event of the function (start, trip or
blocked) is recorded with time stamp and process data values.
Table. 5.4.14. - 135. Event codes of VUB function instances 1-4
Event Number
Event channel
Event block name
Event Code
Description
8320
130
VUB1
0
Start ON
8321
130
VUB1
1
Start OFF
8322
130
VUB1
2
Trip ON
8323
130
VUB1
3
Trip OFF
8324
130
VUB1
4
Block ON
8325
130
VUB1
5
Block OFF
8384
131
VUB2
0
Start ON
8385
131
VUB2
1
Start OFF
8386
131
VUB2
2
Trip ON
8387
131
VUB2
3
Trip OFF
8388
131
VUB2
4
Block ON
8389
131
VUB2
5
Block OFF
8448
132
VUB3
0
Start ON
8449
132
VUB3
1
Start OFF
8450
132
VUB3
2
Trip ON
8451
132
VUB3
3
Trip OFF
8452
132
VUB3
4
Block ON
8453
132
VUB3
5
Block OFF
8512
133
VUB4
0
Start ON
8513
133
VUB4
1
Start OFF
8514
133
VUB4
2
Trip ON
8515
133
VUB4
3
Trip OFF
8516
133
VUB4
4
Block ON
AQ-F255
Instruction manual
Version: 2.00
145
© Arcteq Relays Ltd