Figure. 5.5.4. - 140. Autorecloser shot setting parameters.
Autorecloser shot settings are grouped into corresponding rows where setting of each shot is
straightforward. From the settings can be seen how the reclosing cycle is executed by each request
row by row and which functions initiate requests and which shots and requests are in use.
This setting example presents two shot autoreclosing. For example of the reading of the settings AR1
request is started by I> Start signal and AR2 is started by I0Dir> Trip signal. Timings for AR1 is 500ms
starting time followed by 200ms Dead time which after 200ms Arcing time and 10s Reclaim time for
Shot 1. If Shot 1 fails follows 120s dead time, 200ms Arcing time and 10s Reclaim time. If Shot 2 fails
recloser shall init Final Trip. For AR2 request the reading of the settings is exactly the same, the values
can be read from 2
nd
row. 3
rd
request has just one shot with 60 second dead time. If AR4 or 5
requests are activated, from the corresponding rows from left to right and from up to down can be seen
the autoreclosing schemes for each request.