Figure. 5.5.2. - 121. Simpli ed function block diagram of the OBJ function.
Input signals for object status monitoring
For the function is used available hardware and software digital signal statuses and command signals.
The signals can be divided into Monitor, Command and Control signals based on how they are dealt in
the function. These input signals are also setting parameters for the function. The amount of needed
control and setting parameters depend of the selected object type.
Table. 5.5.2. - 184. Monitor digital signal inputs used by the OBJ function.
Signal
Range
Description
Objectx
Open Input
DI1 …
DIx
(SWx)
Link to the physical binary input. Monitored object OPEN status. “1” means active open state of the
monitored object. Position indication can be done among binary inputs and protection stage
signals by using IEC-61850, GOOSE or logical signals.
Objectx
Close Input
DI1 …
DIx
(SWx)
Link to the physical binary input. Monitored object CLOSE status. “1” means active close state of
the monitored object. Position indication can be done among binary inputs and protection stage
signals by using IEC-61850, GOOSE or logical signals.
WD Object
In
DI1 …
DIx
(SWx)
Link to the physical binary input. Monitored withdrawable object position IN. “1” means that the
withdrawable object cart is in. Position indication can be done among binary inputs and protection
stage signals by using IEC-61850, GOOSE or logical signals.
WD Object
Out
DI1 …
DIx
(SWx)
Link to the physical binary input. Monitored withdrawable object position OUT. “1” means that the
withdrawable object cart is pulled out. Position indication can be done among binary inputs and
protection stage signals by using IEC-61850, GOOSE or logical signals.
Object
Ready
DI1 …
DIx
(SWx)
Link to the physical binary input. Monitored object status.“1” means that the object is ready and
spring is charged for close command. Position indication can be done among binary inputs and
protection stage signals by using IEC-61850, GOOSE or logical signals. Ready status can be set
by application either “1” or “0”.
Syncrocheck
permission
DI1 …
DIx
(SWx)
Link to the physical binary input or synchrocheck function.“1” means that the synchrocheck
conditions are met and object can be closed. Position indication can be done among binary inputs
and protection stage signals by using IEC-61850, GOOSE or logical signals.
Open Block
Input
DI1 …
DIx
(SWx)
Link to the physical or software binary input.“1” means that the opening of the object is blocked.
Position indication can be done among binary inputs and protection stage signals by using IEC-
61850, GOOSE or logical signals.
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
212