Figure. 5.5.8. - 160. First order low pass lter
Curve signal out of range activates “out of range” -alarm that can be used inside logic or with other
relay functions. The signal can be assigned directly to output relay or LED in IO matrix. Out of range
signal is activated when measured mA signal falls below the set input minimum or exceeds the input
maximum limit. Out of range signal is valuable when for example 4…20mA input signal is used.
Figure. 5.5.8. - 161. If in some case the mA input signal is lost, the value will be xed in to the last actual measured cycle value
(value will not go to minimum if it has been something else when signal breaks).
Figure. 5.5.8. - 162. Example of the effects mA input channel settings have.
Table. 5.5.8. - 216. mA Output settings and indications
Name
Range
Step
Default
Description
Curve1...4
updatecycle
5...10000ms
5ms
150ms
mA input measurement update cycle. For fast operation a lower
setting should be implemented.
Scaled value
handling
0:Floating
point
1:Integer out
(Floor)
2:Integer
(Ceiling)
3:Integer
(Nearest)
n/a
0:Floating
point
Rounds the milliamp signal output as selected,
Input value 1
0...4000
0.00001 0
Measured milliamp input value at curve point 1.
AQ-F255
Instruction manual