mA option card 2
Enable mA Out Channels 5&6
0:Disabled
1:Enabled
0:Disabled
Enables mA output cards outputs.
Enable mA Out Channels 7&8
Figure. 5.5.8. - 158. Example of the effects mA output Channel settings have.
Table. 5.5.8. - 212. mA output channel settings
Name
Range
Step
Default
Description
Enable mA Out
Channel
0:Disabled
1:Enabled
-
0:Disabled
Enables the mA Output channel. If channel is disabled
channel settings are hidden.
mA Out
Channel
Magnitude
selection
0:Currents
1:Voltages
2:Powers
3:Imp./Adm.
4:Other
-
0:Currents
De nes the category of measurement used for mA output
control.
mA Out
Channel
Magnitude
Dependent on
category
selection
-
Dependent
on category
selection
De nes the measurement used for mA output control.
Available measurements depends on parameter mA Out
Channel Magnitude selection.
Input value 1
-10
7
…10
7
0.001
0
First input point in the mA output control curve.
Scaled mA
output value 1
0.00000…
24.00000mA
0.0001mA 0mA
mA output value when measured value is equal or less than
Input value 1.
Input value 2
-10
7
…10
7
0.001
1
Second input point in the mA output control curve.
Scaled mA
output value 2
0.00000…
24.00000mA
0.0001mA 0mA
mA output value when measured value is equal or greater
than Input value 2.
Table. 5.5.8. - 213. Hardware indications
Name
Range
Step
Description
mA Output 1-4 Hardware
found
0=None;
1=SlotA;
2=SlotB;
3=SlotC;
4=SlotD;
5=SlotE;
6=SlotF;
7=SlotG;
8=SlotH;
9=SlotI;
10=SlotJ;
11=SlotK;
12=SlotL;
13=SlotM;
14=SlotN;
15=Too many cards
installed
-
Indicates in which option card slot mA output card is
located in.
mA Output 5-8 Hardware
found
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
262