Figure. 5.6.1. - 165. System in case when secondary circuit fault is found in phase L1 wiring.
When fault is detected and all of the conditions are met the CTS timer will start counting. If the situation
continues until the set time has been spent CTS will issue alarm.
Figure. 5.6.1. - 166. System in case when primary circuit fault is found in phase L1 wiring.
Distinction in between primary and secondary fault in this case is impossible. However the situation
meets the CTS conditions and as well as in the secondary circuit fault the CTS will issue alarm if this
state continues until the set time has been spent. This means that the CTS do not supervise only the
secondary circuit but also the primary circuit.