In following chapters common functionalities of protection functions are described. If some protection
function deviates from this basic structure the difference is described in the corresponding chapter of
the manual.
Pick-up characteristics
Pick-up of the function is controlled by Xset setting parameter, which de nes the maximum or minimum
allowed measured magnitude in per unit, absolute or percentage value before function takes action.
The function constantly calculates the ratio between the user set pick-up parameter and measured
magnitude (Im). Reset ratio of 97 % is inbuilt in the function and is always related to the Xset value. If
function pick-up characteristics vary from this description, it is de ned in the function part of the
manual.
Figure. 5.4.1. - 22. Pick up and reset characteristics of the function.
The pick-up activation of the function is not directly equal to start-signal generation of the function.
Start signal is allowed if blocking condition is not active.
Figure. 5.4.1. - 23. Measurement range in relation to the nominal current.
AQ-F255
Instruction manual
Version: 2.00