Settings
Table. 5.2.1. - 7. Settings of the Phase CT scaling.
Name
Range
Step
Default
Description
Scale
meas to In
0:CT nom
p.u.
1:Object In
p.u.
-
0:CT nom
p.u.
Selection of the IED per unit system scaling reference, either the set phase
current CT primary or protected object nominal current.
Phase CT
primary
1…
25000.000A 0.001A 100.000A Rated primary current of the CT in amperes.
Phase CT
secondary
0.200…
10.000A
0.001A 5.000A
Rated secondary current of the CT in amperes.
Nominal
current In
1…
25000.000A 0.001A 100.000A
Protected object nominal current in amperes. (This setting is visible if
“Scale meas to In” setting is set to “Object In p.u.”)
IL1
Polarity
0:-
1:Invert
-
0:-
IL1 ( rst current) measurement channel polarity (direction) selection.
Default setting is that positive current flow is from connector 1 to connector
2 and the secondary currents starpoint is towards line.
IL2
Polarity
0:-
1:Invert
-
0:-
IL2 (second current) measurement channel polarity (direction) selection.
Default setting is that positive current flow is from connector 3 to connector
4 and the secondary currents starpoint is towards line.
IL3
Polarity
0:-
1:Invert
-
0:-
IL3 (third current) measurement channel polarity (direction) selection.
Default setting is that positive current flow is from connector 5 to connector
6 and the secondary currents starpoint is towards line.
CT
scaling
factor P/S
-
-
-
IED feedback value, this is the calculated scaling factor for primary
/secondary current ratio
CT
scaling
factor
NOM
-
-
-
IED feedback value, this is the calculated ratio in between of set primary
and nominal currents.
Ipu
scaling
primary
-
-
-
IED feedback value, scaling factor from p.u. value to primary current.
Ipu
scaling
secondary
-
-
-
IED feedback value, scaling factor from p.u. value to secondary current.
Table. 5.2.1. - 8. Settings of the residual I01 CT scaling.
Name
Range
Step
Default
Description
I01 CT
primary
0.2…
25000.000000A 0.00001A 100.0A
Rated primary current of the CT in amperes.
I01 CT
secondary
0.1…
10.00000A
0.00001A 5.0A
Rated secondary current of the CT in amperes.
I01
Polarity
0:-
1:Invert
-
0:-
I01 (coarse residual) measurement channel polarity (direction)
selection. Default setting is that positive current flow is from connector
7 to connector 8.
CT scaling
factor P/S
-
-
-
IED feedback value, this is the calculated scaling factor for primary
/secondary current ratio
Table. 5.2.1. - 9. Settings of the residual I02 CT scaling.
Name
Range
Step
Default
Description
I02 CT
primary
0.2…
25000.0A 0.00001A 100.0A
Rated primary current of the CT in amperes.
AQ-F255
Instruction manual
Version: 2.00
21