AR
Enabled
in SG
0:Disabled
1:Enabled
8
Selection of the autoreclosing activation in current setting group. It is possible to disable /
enable autoreclosing in each setting group independently. This selection can be changed
dynamically by setting group selection in real time in the IED. Default setting is Disabled.
Manual
resetting
0:Required
1:Obj
Close
resets
8
Selection of the autorecloser resetting after locking ( nal trip, error condition), can be set so
that only manual reset to resetting input of the function resets autorecloser or general breaker
close command from any source resets the autorecloser. This selection can be changed
dynamically by setting group selection in real time in the IED. Default setting is Manual reset
required.
General
reclaim
0:Only
shot
reclaim
1:Shot
reclaim
and
general
reclaim
8
Selections if autorecloser runs after successful reclose (including shot reclaim time) the general
reclaim (object close reclaim time) in which if request for autoreclosing is applied will direct the
autorecloser to locked state. If enabled this selection will de ne the minimum time allowed in
between of autoreclosing cycles without changing the shot speci c reclaim times. This
selection can be changed dynamically by setting group selection in real time in the IED. Default
setting is Only shot reclaim.
Object
close
reclaim
0.000…
1800.000s
by step of
0.005s
8
Setting for general/object close reclaim time. This time starts when the object is manually
closed or if general reclaim time is selected after successful autoreclosing. If during this time
autoreclosing request is applied autorecloser will enter to locked state preventing further
reclosing attempts. This selection can be changed dynamically by setting group selection in
real time in the IED. Default setting is 10.000s.
Lockout
time
0.000…
1800.000s
by step of
0.005s
8
Setting of autorecloser lock-out after successful reclosing. When set to 0.000 recloser enters
directly to ready state after successful reclosing. If this time is running and new reclosing
request is applied autorecloser will enter to locked state preventing further reclose attempts.
This selection can be changed dynamically by setting group selection in real time in the IED.
Default setting is 0.000s (disabled)
Table. 5.5.4. - 195. Autorecloser shot settings.
Setting
Range
SG
Description
AR1,2,3,4,5
Shot
1,2,3,4,5
0:Disabled
1:Enabled
8
Shotx selection enabled / disabled for request ARx. If disabled ARx request will skip
Shot 1 and seek for next enabled shot. If enabled ARx request will execute shot
according to Shot1 settings. This selection can be changed dynamically by setting
group selection in real time in the IED.
AR1,2,3,4,5
Shot
1,2,3,4,5
Starting
delay
0.000…
1800.000s by
step of 0.005s
8
Shotx Starting Delay. This setting de nes the minimum time ARx request has to be
active before entering to Dead time delay counting. This setting is used only when the
ARx request is made from function Start signal. If set with function Trip request to
other than 0.000s value will prevent autoreclosing from starting. When the shot is not
rst one in all cases this setting should be set to 0.000s. This selection can be
changed dynamically by setting group selection in real time in the IED. Default setting
0.000s.
AR1,2,3,4,5
Shot
1,2,3,4,5
DeadTime
delay
0.000…
1800.000s by
step of 0.005s
8
Shotx Dead Time delay. This setting de nes the breaker open time before autorecloser
closes the breaker. Time calculation starts from breaker open signal. This selection
can be changed dynamically by setting group selection in real time in the IED. Default
setting 0.000s.
AR1,2,3,4,5
Shot
1,2,3,4,5
Arc or
Discr.
0:Arcing
1:Discrimination 8
Shotx selection for the action after Dead Time in case fault persists when the breaker
is closed. Selection of Arcing or Discrimination behavior depends of the application.
When arcing time is selected autorecloser shall keep the breaker closed until Action
time is spent and with Discrimination time if during Action time new request is
activated recloser shall lock-out during the Reclaim time. This selection can be
changed dynamically by setting group selection in real time in the IED. Default setting
is Arcing time.
AR1,2,3,4,5
Shot
1,2,3,4,5
Action time
0.000…
1800.000s by
step of 0.005s
8
Shotx Action time setting after Dead Time and breaker is closed. This setting de nes
maximum arcing time or discrimination time when Reclaim time is running. When set
to 0.000s Arcing or Discrimination time is disabled in the autoreclosing scheme. This
selection can be changed dynamically by setting group selection in real time in the
IED. Default setting 0.000s.