Figure. 5.4.9. - 61. Dedicated CBFP operation from binary input signal.
In this mode the CBFP operates from binary input signal only. Additionally also current and output relay
monitoring can be used. The counter for the CBFP is started when the digital input is activated. If the
counter is active until the time in the CBFP counter is used the IED will issue CBFP command to the
incomer breaker. In this application all of the outgoing feeders IED:s tripping signals can be connected
to one dedicated CBFP IED which operates either on current based or all possible faults CBFP
protection.
Events and registers
The CBFP function generates events and registers from the status changes of Retrip, CBFP activated
and blocked signals as well as from the internal pick-up comparators. To main event buffer is possible
to select status “On” or “Off” messages.
Function includes 12 last registers where the triggering event of the function (Retrip, CBFP activated or
blocked) is recorded with time stamp and process data values.
Table. 5.4.9. - 103. Event codes of the CBFP function instance
Event Number
Event channel
Event block name
Event Code
Description
2816
44
CBF1
0
Start ON
2817
44
CBF1
1
Start OFF
2818
44
CBF1
2
Retrip ON
2819
44
CBF1
3
Retrip OFF
2820
44
CBF1
4
CBFP ON
AQ-F255
Instruction manual
Version: 2.00
© Arcteq Relays Ltd
114