HP-IB Address
Each device on the
HP-IB
(
IEEE-488
) interface must have a unique
address. You can set the meter’s address to any value between 0 and 31.
The address is set to “22” when the meter is shipped from the factory.
The
HP-IB
address is displayed when you turn on the meter.
The HP-IB address can be set only from the front-panel.
•
The address is stored in
non-volatile
memory, and
does not
change
when power has been off or after a remote interface reset.
•
You can set the address to “31” which is the
talk only
mode. In this
mode, the meter can output readings directly to a printer without
being addressed by a bus controller. Address 31 is
not
a valid address
if you are operating the multimeter from the
HP-IB
interface with a
bus controller.
•
If you select the
RS-232
interface and then set the
HP-IB
address to the
talk only address (31), the meter will
send
readings over the
RS-232
interface when in the local mode.
•
Your
HP-IB
bus controller has its own address. Be sure to avoid using
the bus controller’s address for
any
instrument on the interface bus.
Hewlett-Packard controllers generally use address “21”.
•
Front Panel operation:
set the address under the
1: HP–IB ADDR
command in the I/O menu.
See also “To Set the HP-IB Address,” on page 188.
Chapter 3 Features and Functions
Remote Interface Configuration
102
GPIB
GPIB
GPIB
GPIB
GPIB
GPIB
GPIB
Summary of Contents for 34420A
Page 1: ......
Page 2: ......
Page 13: ...1 Quick Start ...
Page 31: ...2 Front Panel Operation ...
Page 55: ...3 Features and Functions ...
Page 117: ...4 Remote Interface Reference ...
Page 200: ...5 Error Messages ...
Page 213: ...6 Application Programs ...
Page 245: ...6 Chapter 6 Application Programs Microsoft Excel Macro Example 245 ...
Page 246: ...Chapter 6 Application Programs Microsoft Excel Macro Example 246 ...
Page 247: ...7 Measurement Tutorial ...
Page 274: ...8 Specifications ...
Page 279: ...Dimensions Chapter 8 Specifications 34420A Nano Volt Micro Ohm Meter 280 ...
Page 294: ......