Installation
62/ 84
Fresh grease separator plant Lipator-S-RA/Lipator-P-RA
3.3 Electrical installation
WARNING
Electric shock risk in case of improper electrical installation
■
The control must not be connected to the power supply until after the
sanitary installation and electrical installation have been completed.
■
According to EN 12056, electrical connections may only be carried out by
qualified electricians.
■
Electrical connections must be carried out in accordance with the circuit
diagram,
documents enclosed with the product: "Circuit diagram of the
control".
3.3.1 Electrical data
Characteristic data
Power
2.85 kW
Power supply
230 V/50 Hz
Fusing on site
16 A (time lag) or according to the conditions on site
Degree of protection
Control IP 55
3.3.2 Electrical installation
Î
Install the socket with earth contact for the control in accordance with the
manufacturer‘s instructions.
Î
Set up group alarm. The control has a floating contact for transmission of a group
alarm. A cable must be connected in the control to forward the floating contact as a
group alarm.