ABB i-bus
KNX
Commissioning
136 2CDC 505 056 D0208 | SA/S
No.
Function
Object name
Data type
Flags
10
switch
Output A
EIS 1, 1 bit
DPT 1.001
C, W
This communication object is visible if control of the heating actuator is implemented via a 1 bit communication object. The
heating valve is controlled directly using it.
The device receives a switch telegram via the Switch object.
N/O:
Telegram value
1 = valve open
0 = valve closed
N/C:
Telegram value
1 = valve closed
0 = valve open
10
Control value (PWM)
Output A
EIS 6, 1 byte
DPT 5.010
C, W
This communication object is visible if the control of the heating actuator is implemented via a 1 byte communication object,
e.g. within a continuous control. The communication object value [0…255] is determined by the variable mark-to-space ratio
of the valve.
Telegram value
1 = valve closed
0 = valve open
11
Trigger valve purge
Output A
EIS 1, 1 bit
DPT 1.001
C, W
This communication object is enabled if the
yes
option is selected for parameter
Enable function "valve purge"
in the
A:
Function
parameter window.
The valve purge is triggered using this communication object.
Telegram value:
0 = end valve purge, valve will be closed
1 = start valve purge, valve will be opened