ABB i-bus
KNX
Commissioning
SA/S | 2CDC 505 056 D0208 97
2 bit communication object:
Options:
"0" inactive
"2" OFF
"3" ON
•
"0" inactive
: Forced operation is switched off and the output behaves in the same way as with
parameter
Reaction when forced operation and all safety Priority x end
.
•
"2" OFF
: The communication object
Forced operation
is written with the value 2 and the output
is switched off.
•
"3" ON
: The communication object
Forced operation
is written with the value 3 and the output
is switched on.
Contact position if Safety Priority 2
Contact position if Safety Priority 3
The same setting options exist as those for parameter
Contact position if Safety Priority 1
.
Reaction when forced operation
and all Safety Priority x end
Options:
calculate present contact position
ON
OFF
unchanged
This parameter is only visible if forced operation or a Safety Priority x (x = 1, 2 or 3) function is activated.
The contact position of the relay at the end of forced operation and safety priorities is defined here.
•
calculate present contact position
: After forced operation has ended, the switch value is recalculated
and immediately initiated, i.e., the output continues to operate normally in the background during
forced operation, the output is not changed and is only set after safety priorities end.
•
unchanged
: The contact position is retained during forced operation or safety priority. The contact
position only changes when a new calculated switch value is received.