ABB i-bus
KNX
Device technology
16 2CDC 505 056 D0208 | SA/S
2.2.2
Lamp output load, 6 A
Lamps
Incandescent lamp load
1,380 W
Fluorescent lamps T5/T8
Uncorrected
Parallel compensated
DUO circuit
1,380 W
1,380 W
1,380 W
Low-voltage halogen lamps
Inductive transformer
Electronic transformer
Halogen lamps 230 V
1,200 W
1,380 W
1,380 W
Dulux lamp
Uncorrected
Parallel compensated
1,100 W
1,100 W
Mercury-vapor lamp
Uncorrected
Parallel compensated
1,380 W
1,380 W
Switching capacity (switching contact)
Maximum peak inrush current Ip (150
µ
s)
Maximum peak inrush current Ip (250
µ
s)
Maximum peak inrush current Ip (600
µ
s)
400 A
320 A
200 A
Number of electronic ballasts (T5/T8, single
element)
1)
18 W (ABB EVG 1 x 18 SF)
24 W (ABB EVG-T5 1 x 24 CY)
36 W (ABB EVG 1 x 36 CF)
58 W (ABB EVG 1 x 58 CF)
80 W (Helvar EL 1 x 80 SC)
23
23
14
11
10
1)
For multiple element lamps or other types, the number of electronic ballasts must be determined using the peak inrush current of the electronic
ballasts, see Ballast calculation, p. 42.
Device type
Application program
Maximum number of
communication objects
Maximum number of
group addresses
Maximum number of
associations
SA/S 2.6.2.1
Switch 2f 6AM/…*
34
254
254
SA/S 4.6.2.1
Switch 4f 6AM/…*
64
254
254
SA/S 8.6.2.1
Switch 8f 6AM/…*
124
254
254
SA/S 12.6.2.1
Switch 12f 6AM/…*
184
254
254
* … = current version number of the application program
Please note
ETS and the current version of the device application program are required for programming.
The current application program is available for download at
www.abb.com/knx
. After import into ETS it
can be found under
ABB/Output/Binary output xf 6AM/…*
(x = 2, 4, 8 or 12).
The device does not support the locking function of a KNX device in ETS. If you inhibit access to all of
the project devices by using a
BCU code
, it has no effect on this device.
Data can still be read and programmed.