SA/S | 2CDC 505 056 D0208 151
4.2.2.2
ON/OFF delay
The ON/OFF delay delays output switch-on or switch-off.
The delay time T
D1
or T
D0
starts after a switch telegram, and after it has elapsed, the output executes the
switch telegram.
If a new ON telegram with the value 1 is received during the switching ON delay, the ON delay time starts
again. Likewise, If a new OFF telegram with the value 0 is received during the switching OFF delay,
the OFF delay time starts again.
Please note
If the device receives an OFF telegram during the switching on delay time T
D1
, an ON telegram is
disregarded.